HVAC Diagnostic Service — Diagnostic service, dual run capacitor
- HVAC
On July 26, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 1104 Yale Avenue, Richmond Heights, MO 63117.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$505
Performed a diagnostic service and supplied a dual run capacitor.
- HVACWork status not resolved
Photograph shows an outdoor HVAC condenser unit with heavily fouled/darkened coils visible through the wire guard, dense vegetation and vines growing around and through the unit on all sides, and a multimeter resting on top of the unit.
- HVACWork status not resolved
Photograph shows an outdoor air conditioning condenser unit with a top-mounted fan and grille, surrounded by heavy overgrown vegetation; a loose cylindrical capacitor and a yellow electrical testing device are visible on top of the unit, and the condenser coil fins appear dirty with debris accumulation.
- HVACWork status not resolved
a wire mesh guard surrounds the unit and tools/hoses are visible on top
- HVACWork status not resolved
Fieldpiece app measurements show air-side Delta T of 15.9°F (return dry bulb 82.8°F, supply 66.9°F), supply relative humidity 95.9%, and refrigerant-side suction pressure 103.1 psig with liquid pressure 220.5 psig.
- HVACWork status not resolved
Photograph shows Fieldpiece app live refrigerant diagnostic readings for an R-22 system: suction pressure 103.1 psig, liquid pressure 221.2 psig, Delta T 16.0°F, actual superheat 16.6°F, actual subcooling 6.9°F, suction temp 77.2°F, liquid temp 101.4°F.
- HVACWork status not resolved
Photograph shows a Fluke 323 True RMS Clamp Meter being held outdoors near what appears to be mechanical/electrical equipment, with the dial set to AC amperage mode and the LCD display active.
- HVACWork status not resolved
Photograph shows a technician using a Fluke True RMS multimeter to test a round run capacitor on an outdoor HVAC condenser unit; the capacitor has blue and yellow wires attached and the unit's top panel shows significant dirt and debris accumulation.