- HVAC · Refrigerant recharged with 6 pounds of R-410A added · Jul 2026
- HVAC · Rooftop condenser coil fins visibly packed with debris and lint · 2026
- HVAC · Rooftop unit interior shows heavily soiled blower wheel · 2026
RECORD SUMMARY
Fresh House preserves inspections, repairs, and appraisals so a home's history is never lost.
This page contains 3 documented records for 13491 Olive Boulevard, Chesterfield, MO 63017, dated from June 2026 through July 2026. The amount summary includes $1,619 in completed work across HVAC; appraisal values and permit-declared valuations are excluded.
HVAC Diagnostic Service — Commercial diagnostic, return trip
- HVAC
Built from Housecall Pro data
- $489HVACDiagnostic service, return trip, and two hours of commercial labor performed during normal business hours.
- HVACPhotograph shows a close-up view of an HVAC air filter or return air grille with metal louvers; the filter media behind the slats is heavily loaded with dark gray dust, lint, and particulate debris, indicating a significantly clogged filter in need of replacement.
- HVACPhotograph shows a rooftop HVAC condenser unit with louvered coil guards; condenser fins appear darkened with debris accumulation, and the metal roof curb below exhibits visible rust and corrosion staining.
- HVACPhotograph shows HVAC condenser coil fins with heavy accumulation of dust, dirt, lint, and fibrous debris packed along the top edge and throughout the fin rows, significantly restricting airflow.
- HVACPhotograph shows interior of an open rooftop HVAC condensing unit with condenser fan assembly, compressor, copper refrigerant lines showing oxidation/corrosion, and handwritten notation 'R-448A / 6.5 #' on the accumulator/compressor; debris accumulation and rust visible on the unit frame.
- HVACPhotograph shows a circular dual-scale analog gauge (°F outer / °C inner, range -40 to 60°F) mounted on a white metal surface, with the needle reading approximately 30°F / 0°C; visible rust and brown staining are present on the surface below and around the gauge housing.
HVAC
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Service Invoice — No-charge service visit
- HVAC
Built from Housecall Pro data
Only original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Diagnostic and Refrigerant Service — 6 lbs R-410A refrigerant
- HVAC
Built from Housecall Pro data
- $1,130HVACPerformed commercial overtime diagnostic and 2 hours of overtime labor, and added 6 pounds of additional R-410A refrigerant.
- HVACFieldpiece app refrigerant side measurements show R-410A system with suction pressure 123.8 psig, liquid pressure 343.4 psig, actual superheat 27.3°F, and actual subcooling 3.7°F.
- HVACPhotograph shows Fieldpiece app screen displaying live R-410A refrigerant measurements: suction pressure 126.9 psig, suction temperature 61.7°F, vapor saturation 43.6°F, actual superheat 18.1°F; liquid pressure 364.7 psig, liquid temperature 91.5°F, liquid saturation 109.6°F, actual subcooling 18.1°F, discharge pressure 364.7 psig.
- HVACFieldpiece app refrigerant side measurements for R-410A system show suction pressure 126.2 psig, liquid pressure 356.2 psig, actual superheat 27.7°F, and actual subcooling 4.2°F.
- HVACPhotograph shows a heavily soiled, clogged air filter inside an HVAC air handler cabinet, with significant dust and debris accumulation on the filter surface and loose fibrous debris collected on the cabinet floor beneath it.
- HVACPhotograph shows Fieldpiece app screen displaying live R-410A refrigerant-side measurements: suction pressure 125.1 psig, liquid pressure 341.4 psig, actual superheat 16.7°F, and actual subcooling 13.8°F.
- HVACPhotograph shows Fieldpiece app refrigerant-side measurements for R-410A system: suction pressure 121.0 psig, suction temperature 70.1°F, vapor saturation 41.0°F, actual superheat 29.1°F; liquid pressure 328.8 psig, liquid temperature 97.9°F, liquid saturation 102.2°F, actual subcooling 4.3°F, discharge pressure 328.8 psig.