HVAC Maintenance — Hard start kit and breaker supplied
- HVAC
On August 10, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 1445 Roth Hill Drive, Maryland Heights, MO 63043.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$350
Service call with a new hard start kit supplied and a new breaker supplied for the existing Siemens panel.
- HVACWork status not resolved
Resident reports air conditioner is not cooling and the A/C breaker keeps tripping; troubleshooting confirmed thermostat set correctly and vents open, with probable diagnosis of AC blowing cold air but home remaining too hot.
- HVACWork status not resolved
Fieldpiece refrigerant side measurements show R-410A system with suction pressure 153.4 psig, liquid pressure 365.5 psig, actual superheat 3.8°F, and actual subcooling 6.8°F.
- HVACWork status not resolved
Photograph shows a residential outdoor air conditioning condenser unit mounted on a concrete pad against the house foundation, with a disconnect box mounted on the siding above, and an open technician tool bag placed to the left of the unit.
- HVACWork status not resolved
condenser coil fins visible through the grille appear dirty and clogged with debris, cobwebs, and plant material
- HVACWork status not resolved
Photograph shows an outdoor HVAC condenser unit with access panel open, exposing a Supco Super Relay hard-start kit mounted inside, a dual-run capacitor (labeled 50/5), a contactor/relay held by a technician's hand, and multiple colored wiring connections.
- HVACWork status not resolved
Photograph shows the interior of a residential electrical panel containing multiple Siemens circuit breakers, including single-pole 15A and 20A breakers, double-pole 30A breakers, tandem (double-tap) breakers rated 20A, and what appear to be AFCI/GFCI breakers with test buttons; multiple conductors including red, black, and white wiring are visible connected to the bus bars.
- HVACWork status not resolved