HVAC Refrigerant Service — R-22 refrigerant added (2 lb max)
- HVAC
On August 27, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 2194 Francis Drive, Arnold, MO 63010.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$425
Added R-22 refrigerant (2 lb. max) to the HVAC system and charged the system; trip fee applied.
- HVACWork status not resolved
Photograph shows Fieldpiece app live refrigerant diagnostic readings for an R-22 system: suction pressure 67.3 psig, liquid pressure 239.2 psig, actual superheat 21.4°F, actual subcooling 13.2°F; air-side diagnostics indicate adequate airflow across the evaporator coil.
- HVACWork status not resolved
Fieldpiece diagnostic app shows R-22 system with dry bulb at 58.8°F (target 61.1°F) indicating adequate airflow across the evaporator coil, and actual superheat close to target superheat of 20.7°F indicating adequate refrigerant charge for a fixed metering device.
- HVACWork status not resolved
Fieldpiece app measurements show air-side Delta T of 19.6°F (return dry bulb 78.5°F, supply dry bulb 58.9°F), return RH 55.0%, supply RH 79.2%, and refrigerant-side suction pressure 67.3 psig with liquid pressure 239.2 psig.
- HVACWork status not resolved
model UAKB-042JAZ, serial 6953F150403653, manufactured 04/2004, 208/230V single-phase, R22 refrigerant, 79 oz. factory charge