HVACCompleted work
AC maintenance was performed.
HVACWork status not resolved
Photograph shows an outdoor HVAC condenser unit with the louvered side grille heavily packed with dirt, dust, leaves, and organic debris, significantly obstructing airflow through the condenser coil fins.
HVACWork status not resolved
Photograph shows a camera monitor screen displaying the interior of a ribbed/corrugated pipe with visible discoloration and buildup along the walls; camera unit reads 105°F and timestamp 04-29-2026 16:18.
HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge set connected to refrigerant lines, displaying R410A readings: superheat (SH) 12.3°F, subcooling (SC) 16.5°F, low-side pressure 105.1 psi, high-side pressure 268.7 psi.
HVACWork status not resolved
Photograph shows an outdoor AC condenser unit with visibly dirty condenser coil fins, with significant dust, dirt, and debris accumulation embedded throughout the fin array and debris visible at the base of the unit.
HVACWork status not resolved
Photograph shows a Klein Tools CL390 clamp meter clamped around wiring at an HVAC unit, displaying a current reading of 06.79 A (AC) on its digital display.
HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an outdoor R-410A condenser unit, displaying low-side pressure of 112.4 psi, high-side pressure of 305.4 psi, superheat (SH) of 3.0°F, and subcooling (SC) of 19.9°F.
HVACWork status not resolved