- HVAC · R-410A refrigerant added to the HVAC system · Jul 2026
- HVAC · Diagnostic readings indicated possible low refrigerant capacity · 2026
RECORD SUMMARY
Fresh House preserves inspections, repairs, and appraisals so a home's history is never lost.
This page contains 1 documented record for 2534 Tanglewood Drive, Arnold, MO 63010. The amount summary includes $249 in completed work across HVAC; appraisal values and permit-declared valuations are excluded.
HVAC Refrigerant Service — 2 lbs R-410A refrigerant added
- HVAC
Built from Housecall Pro data
- $249HVACAdded 2 pounds of additional R-410A refrigerant to the HVAC system and a trip fee was charged.
- HVACFieldpiece refrigerant diagnostic shows R-410A system with suction pressure 78.8 psig, liquid pressure 297.9 psig, actual superheat 55.9°F, and actual subcooling 0.7°F; air-side diagnostics indicate supply dry bulb (71.8°F) is above target (61.5°F), suggesting low capacity possibly due to refrigerant mischarge or dirty condenser coils.
- HVACPhotograph shows an A-frame evaporator coil assembly with extensive rust and corrosion on the coil headers, fins, and surrounding metal surfaces; copper refrigerant tubing is visible with discoloration consistent with age and moisture exposure.
- HVACFieldpiece app diagnostic measurements show air-side Delta T of 15.4°F (return dry bulb 77.0°F, supply dry bulb 61.6°F), return RH 61.8%, supply RH 90.4%, and refrigerant-side suction pressure 141.5 psig with liquid pressure 373.3 psig.