Hi, I'm 3160 Morganford Road. I only speak from this property's source-backed records — 2 documents from 1 contributor. If there's no record, I'll tell you I don't know rather than guess. Every claim links to its source.
3160 Morganford Road
Across 2 records on this property
Completed work
Invoices and paid receipts
Estimated · not confirmed
Quotes, estimates, and other amounts not confirmed as performed
Fresh House Property Summary
Highlights selected from 2 documented records for this property.
- HVAC · HVAC diagnostic service call performed on the system · Sep 2026
- HVAC · Second HVAC service call made the following month · Oct 2026
- HVAC · RTU1 control board lost communication; no cooling delivered · 2026
- HVAC · Outdoor temp sensor arrived on site; installation not yet scheduled · 2026
RECORD SUMMARY
Fresh House preserves inspections, repairs, and appraisals so a home's history is never lost.
This page contains 2 documented records for 3160 Morganford Road, St. Louis, MO 63116, dated in October 2026. The amount summary includes $479 in completed work across HVAC; appraisal values and permit-declared valuations are excluded.
HVAC Diagnostic Service — and labor
- HVAC
Built from Housecall Pro data
- $260HVACPerformed a diagnostic service and residential labor at the property.
- HVACPhotograph shows the interior of an outdoor electrical junction box (P/N ZSO-SH-3-6-B, S/N ZSO46000WQ) with severe rust, corrosion, and brown staining throughout the housing and around multiple wire entry points, including green, black, red, white, and orange conductors.
- HVACPhotograph shows a BAS control screen for an occupied AHU: RAT 90.8°F, SAT 60.3°F, MAT 95.1°F, OAT 72.0°F, Comp 1 On/Comp 2 Off in cooling mode, CO2 at 2000.0, zone temp 78.6°F, economizer enabled, building pressure 0.02 in H2O vs setpoint 0.050 in H2O.
- HVACPhotograph shows a ZS Outdoor Temp/Humidity Sensor mounted inside a gray metal outdoor enclosure, with a probe extending downward fitted with a sintered metal filter cap; some discoloration is visible on the sensor housing.
HVAC
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Service Call — Trip fee and commercial labor
- HVAC
Built from Housecall Pro data
- $219HVACTrip fee and commercial labor service call performed at the property.
- HVACPhotograph shows a 'ZS Outdoor Temp/Humidity Sensor' in a weatherproof enclosure mounted on the exterior panel of a rooftop HVAC air handling unit, with a yellow handheld digital meter (SPK2) displaying a reading of 60.2 visible nearby.
- HVACLouis, MO): RTU1 I/O Flex board is in comm loss with EMS and no cool air blowing an outdoor temp sensor has arrived on site and needs to be scheduled for installation
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
Only the original contributor can modify this entry · Create an account to manage your contributions over time.
Add inspections, repairs, appraisals,
or anything that shaped this property.