Record 1Public property record

HVAC Diagnostic Service — Commercial OT diagnostic

  • HVAC

On January 24, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 35 Gravois Bluffs Plaza Drive, Fenton, MO 63026.

Record date

Documented details

  • Outcome: Paid in full

Available findings

  • HVACCompleted work$290

    Performed a commercial OT diagnostic at the service address.

  • HVACWork status not resolved

    Photograph shows a heavily corroded and rusted metal panel or heat exchanger component inside an HVAC unit, with extensive orange-brown oxidation, pitting, and apparent moisture weeping across the surface; multiple wiring bundles are also visible routed through the cabinet interior.

  • HVACWork status not resolved

    Photograph shows a dirty HVAC equipment data plate with model 48TFD007 (suffix partially obscured), serial number 1303G50099, using R-22 refrigerant with a system charge of 9.0 lbs (4.1 kg).

  • HVACWork status not resolved

    Photograph shows significant rust and corrosion at the junction of a cylindrical metal tube and a larger sheet metal component, consistent with HVAC heat exchanger or burner tube assembly; surrounding metal panels and fasteners also show surface oxidation.

  • HVACWork status not resolved

    Photograph shows multiple metal heat exchanger or burner tubes with extensive surface rust, corrosion, and pitting throughout; degraded fibrous insulation material is also visible at the base of the assembly.

  • HVACWork status not resolved

    Photograph shows a furnace heat exchanger with severe corrosion, heavy rust accumulation, and two visible open holes/ports in the deteriorated metal, indicating significant structural degradation of the component.

  • HVACWork status not resolved

    Photograph shows sheet metal ductwork in what appears to be a crawl space, with significant rust and corrosion visible along duct seams and joints, and fibrous debris/insulation material visible below.

Record 2Public property record

HVAC Heat Exchanger Invoice — Carrier OEM heat exchanger supplied

  • HVAC

On January 26, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 35 Gravois Bluffs Plaza Drive, Fenton, MO 63026.

Record date

Documented details

  • Outcome: Paid in full

Available findings

  • HVACCompleted work$5,100

    Supplied a Carrier OEM heat exchanger.

  • HVACWork status not resolved

    Photograph shows heat exchanger tubes inside an HVAC unit with heavy rust, surface corrosion, and deterioration throughout, along with degraded fibrous insulation material visible at the base.

  • HVACWork status not resolved

    Photograph shows the interior of a gas furnace with the access panel removed, revealing two corrugated clamshell-style heat exchanger sections, associated wiring (red and blue leads), and heavily deteriorated, discolored, and compressed fiberglass insulation lining the bottom of the furnace cabinet.

  • HVACWork status not resolved

    Photograph shows an HVAC unit data plate with model 48TFD007 (suffix partially obscured), serial number 1303G50099, using legacy R-22 refrigerant with a system charge of 9.0 lbs (4.1 kg).

  • HVACWork status not resolved

    Photograph shows an interior HVAC panel or access cover with severe, widespread rust and corrosion across its surface, along with visible moisture droplets; multiple wiring bundles are present in the surrounding cabinet.

  • HVACWork status not resolved

    Photograph shows significant rust and corrosion at a flanged pipe joint on what appears to be an HVAC unit, with orange-brown oxidation staining spreading onto adjacent sheet-metal surfaces and visible deterioration at the weld/seam area.

  • HVACWork status not resolved

    Photograph shows a rooftop packaged HVAC unit on a flat commercial roof with heavy snow accumulation surrounding the unit base; exposed black refrigerant/piping lines are visible protruding from the snow to the right of the unit.

  • HVACWork status not resolved

    Photograph shows an open HVAC unit with the access panel removed, exposing a blower motor assembly, a large bundle of disorganized multi-colored wiring, corroded/rusty structural rails, a control component (possible gas valve) at the base, and surrounding snow and ice on the ground.

  • HVACWork status not resolved

    Photograph shows sheet metal ductwork with heavy rust and corrosion concentrated at a seam/joint, with deterioration visible along the duct edges and surrounding metal surfaces; fibrous debris or insulation material is visible below the ductwork.

  • HVACWork status not resolved

    Photograph shows severe rust and corrosion covering a large metal panel inside an HVAC cabinet, with active-appearing oxidation and moisture present; multiple wiring bundles are routed nearby.

  • HVACWork status not resolved

    Photograph shows a downed parking lot light pole lying on wet asphalt with exposed multicolored wiring visible at the base, adjacent to a service vehicle in a snow-covered parking lot.

  • HVACWork status not resolved
Record 3Public property record

HVAC Thermostat Installation — Non-programmable thermostat installed

  • HVAC

On March 12, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 35 Gravois Bluffs Plaza Drive, Fenton, MO 63026.

Record date

Documented details

  • Outcome: Paid in full

Available findings

  • HVACCompleted work$260

    Installed a non-programmable thermostat.

Record 4Public property record

HVAC Actuator Replacement Estimate — Failed economiser actuator

  • HVAC

On March 18, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 35 Gravois Bluffs Plaza Drive, Fenton, MO 63026.

Record date

Available findings

  • HVACEstimate or proposed work$1,275

    Estimate for replacing the failed economiser actuator, which was diagnosed as failed.