HVACCompleted work$434
Performed a commercial diagnostic and 2.5 hours of commercial maintenance-rate labor at the service address.
HVACWork status not resolved
Photograph shows a gray packaged rooftop HVAC unit marked '103' mounted on a metal curb on a flat commercial roof, with a white PVC condensate drain line running across the roof surface and a power drill resting on the curb, suggesting recent or ongoing installation or service work.
HVACWork status not resolved
Photograph shows a large flexible insulated HVAC duct suspended by a black strap from wood ceiling joists in an open ceiling cavity, with pink fiberglass batt insulation visible between joists above.
HVACWork status not resolved
Photograph shows flexible HVAC ductwork in an attic space with a severe kink and apparent damage or deterioration to the outer foil insulation jacket, with pink fiberglass batt insulation and wood framing visible overhead.
HVACWork status not resolved
Photograph shows a UEI EM152 digital manometer displaying a static pressure reading of -1.05 inH2O, with probe tubes connected, resting on a gray metal HVAC unit surface.
HVACWork status not resolved
Photograph shows flexible insulated HVAC ductwork running through an attic or crawl space, with a duct junction on the right side appearing loose or disconnected; pink fiberglass batt insulation is visible on the ceiling deck above.
HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge displaying R454B refrigerant readings: superheat (SH) 15.9°F, subcooling (SC) 7.9°F, low-side pressure 108.5 psi, and high-side pressure 251.6 psi.
HVACWork status not resolved
Photograph shows a recessed light fixture housing (can light) mounted in the attic floor/ceiling deck with a flexible metal conduit attached, pink fiberglass batt insulation along the rafters, a diagonal wooden structural member, and a large dark-wrapped component resting on the deck surface.
HVACWork status not resolved
Photograph shows attic interior with 8-inch R-42 insulated flexible ductwork routed through the space, alongside pink fiberglass batt insulation on the roof deck and loose-fill insulation on the attic floor.
HVACWork status not resolved
Photograph shows large insulated flexible ductwork routed through an attic space alongside metallic armored conduit, with pink fiberglass batt insulation visible and debris on the attic floor decking.
HVACWork status not resolved
Photograph shows a flexible black duct connected to the recessed light housing area within the ceiling plenum, routed upward toward the structural framing above.
HVACWork status not resolved
Photograph shows insulated refrigerant/suction lines inside an HVAC cabinet with surface discoloration, and foil tape on the duct or cabinet edge that is visibly cracked, peeling, and deteriorating with green discoloration beneath.
HVACWork status not resolved