On September 24, 2026, Greensmith Home Inspection llc documented Electrical, Foundation, HVAC, and 7 other topics at 4528 Southridge Pines Drive, St. Louis, MO 63128.
- Record date
Available findings
- Home InspectionWork status not resolved
Whole-home inspection of single-family residence found the home in generally good condition with no structural issues, but identified multiple deficiencies including inoperable smoke detectors, a 1995 water heater near end of life, older termite damage, a PVC lateral line indentation, damaged deck banding board, missing laundry GFCI, master bath faucet leak, broken kitchen window seal, damaged basement drop ceiling framing, and a fireplace flue stuck open.
- ElectricalWork status not resolved
Smoke detectors throughout the home are inoperable and must be replaced laundry room lacks GFCI protection and requires a GFCI outlet installation
- HVACWork status not resolved
gas fireplace operates properly but the flue is stuck open and will not close, requiring repair
- PlumbingWork status not resolved
master bathroom vanity sink has a minor faucet leak requiring repair
- SewerWork status not resolved
Indentation observed in the top of the PVC lateral line approximately 5 feet from the city sewer tie-in requiring repair; main sewer stack cap has been glued shut and needs to be opened with solvent.
- RoofWork status not resolved
Architectural shingle roof estimated to be 5–7 years old is installed correctly and in satisfactory condition; gutters, flashings, soffit, fascia, and ventilation all satisfactory.
- FoundationWork status not resolved
Poured concrete foundation is in satisfactory condition with common cracks noted; inspector recommends sealing cracks with urethane caulk; no moisture intrusion was observed in the basement.
- PestWork status not resolved
Older termite damage is visible on the rear deck and landscaping timber with no other signs of active infestation found throughout the structure
- WindowsWork status not resolved
The window over the kitchen sink appears to have a broken seal and needs repair or replacement; blinds are wrong fit and need replacement; damage inside the window sill also requires repair.
- RadonWork status not resolved
Radon test result is ≥ EPA Action Level with an EPA protocol average of 17.6 pCi/L (overall average 17.3 pCi/L) measured over 44 hours in the basement; EPA recommends mitigation at 4 pCi/L or more.
- SewerWork status not resolved
Sewer lateral inspection found an indentation in the top of the PVC lateral line approximately 5 feet from the city sewer tie-in that needs to be repaired.
- PestWork status not resolved
Older termite damage observed on wood deck and landscape timbers; no live insects found; borate-based spray treatment recommended for affected areas.