HVAC Maintenance Service — AC outdoor unit maintenance and cleaning
- HVAC
On June 24, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 4888 Southridge Park Drive, St. Louis, MO 63129.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$145
Inspected the outdoor condensing unit, checked system pressure and components of the outdoor system, cleaned the outdoor unit and verified it was working properly.
- HVACWork status not resolved
Photograph shows Fieldpiece app refrigerant measurements for an R-410A system: suction pressure 119.2 psig, liquid pressure 256.6 psig, Delta T 21.7°F, actual superheat 1.9°F, actual subcooling 13.2°F.
- HVACWork status not resolved
Photograph shows a Fluke 323 True RMS Clamp Meter displaying a reading of 35 AAC (AC amperes), being held near an insulated wire or conduit running along a painted concrete/stucco exterior surface.
- HVACWork status not resolved
Photograph shows a mobile HVAC diagnostic app screen displaying air-side readings: return dry bulb 70.2°F, supply dry bulb 48.7°F, Delta T 21.5°F, supply relative humidity 93.7%, and liquid-side refrigerant pressure 256.4 psig.
- HVACWork status not resolved
Photograph shows the manufacturer data plate on an outdoor central cooling air conditioner, model 24ABB348A340, serial 3816E06799, factory charged with R410A (7.37 lbs), 208-230V/1PH/60Hz power supply, manufactured September 2016.