HVACCompleted work$89
AC maintenance performed at 5308 Vallarta Drive.
HVACWork status not resolved
Photograph shows an outdoor air conditioning condenser unit installed on a concrete pad against a brick wall; the condenser coil fins appear darkened with dirt and debris accumulation, and a wall-mounted electrical disconnect box with visible wiring is present nearby.
HVACWork status not resolved
Fieldpiece app air-side measurements show return dry bulb 72.0°F / supply 52.0°F, Delta T 20.0°F, return RH 59.1% / supply RH 78.2%; refrigerant side pressures not yet linked.
HVACWork status not resolved
Fieldpiece app refrigerant measurements for R-410A system show suction pressure 113.5 psig, liquid pressure 258.2 psig, actual superheat 15.4°F, and actual subcooling 8.1°F; air side diagnostics unavailable due to tools not in range.
HVACWork status not resolved
Photograph shows an outdoor air conditioning condenser unit mounted on a concrete pad against a brick wall; the condenser coil fins appear darkened and dirty, and an orange garden hose is present nearby, possibly for coil cleaning.
HVACWork status not resolved
Photograph shows an outdoor residential air conditioning condenser unit with top-discharge fan grille and visible condenser coil fins; refrigerant and electrical lines run along the adjacent brick wall, a second condenser unit is partially visible in the background, and weeds/vegetation are growing around the base of the unit.
HVACWork status not resolved
Photograph shows an outdoor air conditioning condenser unit mounted on a concrete pad beside a brick home; condenser coils appear heavily soiled with debris accumulation on the fins, PVC piping and an electrical disconnect box are visible on the adjacent wall, and tools/rags on the ground suggest service work in progress.