- HVAC · HVAC system converted from R-407C to R-22 refrigerant · Jul 2026
- HVAC · Commercial HVAC diagnostic service performed on-site · Sep 2026
- HVAC · Separate commercial HVAC diagnostic service also performed · Jun 2026
- HVAC · Residential HVAC diagnostic service performed · Jun 2026
RECORD SUMMARY
Fresh House preserves inspections, repairs, and appraisals so a home's history is never lost.
This page contains 4 documented records for 610 Jungermann Road, St. Peters, MO 63376, dated from June 2026 through September 2026. The amount summary includes $3,719 in completed work across HVAC; appraisal values and permit-declared valuations are excluded.
HVAC Diagnostic Service — Commercial diagnostic service
- HVAC
Built from Housecall Pro data
- $160HVACCommercial diagnostic service performed at 610 Jungermann Road, St. Peters, Missouri.
- HVACPhotograph shows a gray metal HVAC cabinet panel with a circular knockout hole exhibiting interior rust/corrosion and a visible crack or fracture line extending from the hole, along with an oval embossed feature on the panel surface.
- HVACPhotograph shows a refrigerant line sight glass with a discolored (yellow-green) moisture indicator dot and brownish interior, mounted on heavily corroded refrigerant lines near an outdoor condenser unit.
- HVACPhotograph shows a white-painted pipe tee or elbow fitting on a vertical pipe exhibiting heavily cracked and peeling paint, visible rust/corrosion on the pipe below the fitting, and green and orange-rust colored deposits visible inside the open socket of the fitting, consistent with copper corrosion (verdigris).
- HVACPhotograph shows a large glass panel with dark metal framing and rubber perimeter gasket/seal, positioned at floor level on wood-look tile; a worker's boot is visible at the corner of the unit.
- HVACPhotograph shows a large glass panel with a dark metal frame; consistent with a sliding glass door or window unit; displayed flat on a light-colored subway-tile-pattern floor in what appears to be a retail showroom setting; a person in work boots is standing adjacent to the unit.
- HVACPhotograph shows a large glass panel with black metal frame and rubber gasket; consistent with a commercial refrigerator or display case door; removed from its unit and resting flat on a wood-look ceramic tile floor; colorful canned beverages are visible on shelving in the background reflection.
HVAC
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Diagnostic Service — Residential HVAC diagnostic service
- HVAC
Built from Housecall Pro data
- $89HVACResidential diagnostic service was performed.
- HVACPhotograph shows a Bohn refrigeration unit equipped with a Beacon II Refrigeration System, with a circular LED display reading '41' (likely temperature in °F).
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Refrigerant Conversion — 407-C to R-22 conversion
- HVAC
Built from Housecall Pro data
- $3,200HVACPerformed a 407-C to R-22 conversion.
- HVACPhotograph shows a rooftop HVAC condenser unit being serviced with R-22 refrigerant
- HVACPhotograph shows an HVAC equipment data plate with wiring schematic (ladder diagram) displaying components TDR, C1, RE, HPS, and RED; Model #: BHS050H2C, Serial #: T09B04253; Customer field is blank.
- HVACBHS050H2C7M, minimum circuit ampacity using 75°C wire rated 28A, and a condenser fan motor (QTY: 1, HP: 1/3, FLA: 3.5)
- HVACPhotograph shows a Fieldpiece MG44 wireless vacuum gauge connected to the service valve manifold of an outdoor AC condenser unit, with refrigerant hoses attached; the condenser base frame exhibits visible rust and corrosion.
HVAC
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Diagnostic Service — Commercial HVAC diagnostic service
- HVAC
Built from Housecall Pro data
- $270HVACCommercial HVAC diagnostic service performed with commercial labor during normal business hours.
- HVACBAS dashboard for RTU1.G.1.1.B shows unit in occupied cooling mode: supply air 47.9°F, return air 69.7°F, zone temp 72.4°F, zone humidity 64.0%rh, OAT 79.0°F, compressor Stage 1 On, heating Stage 1 Off, dehumidification active with fan speed and temp setpoint adjusted, CO2 at 517.0, economizer not enabled.