HVAC Diagnostic and Maintenance — Overtime diagnostic
- HVAC
On August 25, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 6638 Clayton Road, Richmond Heights, MO 63117.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$645
Commercial overtime diagnostic performed and 3.5 hours of commercial maintenance labor completed.
- HVACWork status not resolved
Photograph shows a black hermetic scroll compressor labeled 'Compressor No. 1' inside an HVAC unit, with blue and yellow wiring routed around it and copper refrigerant lines connected at the top.
- HVACWork status not resolved
Photograph shows a mobile HVAC diagnostic app screen for a 1-ton split system in cooling mode displaying refrigerant readings: LP 139.0 PSIG, HP 336.1 PSIG, EVAP 48.5°F, COND 103.9°F, SLT 64.3°F (elevated, up arrow), LLT 94.2°F, SH 15.9°F (OK), SC 9.8°F (OK), nAF 400 SCFM (OK); all airside temperature and pressure fields are blank; the Diagnostics button shows a red flag alert.
- HVACWork status not resolved
Photograph shows the interior lower compartment of an HVAC air handler or furnace with multiple electrical wires (blue, yellow, red, black, and white) routed through a wire channel, all heavily coated with accumulated dust and debris; the wire retaining clips and surrounding sheet metal surfaces are similarly fouled.
- HVACWork status not resolved
Photograph shows a mobile HVAC diagnostic app screen for a 1-ton split system in cooling mode displaying refrigerant readings: LP 139.0 PSIG, HP 336.1 PSIG, EVAP 48.5°F, COND 103.9°F, SLT 64.3°F (elevated, red up-arrow), LLT 94.2°F, SH 15.9°F (pass), SC 9.8°F (pass), nAF 400 SCFM (pass); Diagnostics button shows a red flag alert; all airside temperature and pressure fields are blank.
- HVACWork status not resolved
Photograph shows the filter access panel of a rooftop HVAC unit with hand-written notation '2- 16x25x2' indicating two 16x25x2 filters
- HVACWork status not resolved
Photograph shows a large flexible silver HVAC duct running along the upper wall/ceiling junction, and a boxed Sensi brand thermostat sitting on top of a storage cabinet, suggesting a thermostat replacement or installation is pending.
- HVACWork status not resolved
Photograph shows the interior of an HVAC air handler unit with a large centrifugal blower wheel driven by a belt-and-pulley system connected to a motor; visible conditions include heavy dust and dirt accumulation on the blower wheel and housing, rust on the blower shaft hub, and a drive belt showing wear.
- HVACWork status not resolved
Photograph shows a squirrel-cage blower wheel with heavy accumulation of dust and debris coating all visible fan blades, indicating significant lack of maintenance cleaning.
- HVACWork status not resolved
Photograph shows the interior of a large HVAC unit with a belt-drive blower assembly featuring two toothed drive belts, multiple pulleys, a blower wheel, an auxiliary motor, and routed electrical wiring; components show visible dust accumulation and wear.
- HVACWork status not resolved
Photograph shows the data plate of a Johnson Controls forced air furnace with cooling unit, model ZXG06M2B1AA1A111A1, serial N1B4432850, rated 208/230V–3–60Hz, factory charged with R410A refrigerant, and rated at 90,000 BTU/H normal input.
- HVACWork status not resolved
Photograph shows the manufacturer's data plate on an outdoor forced air furnace with cooling unit; model ZXG06M2B1AA1A111A1, serial N1B4432850, factory charged with R410A refrigerant, rated 208/230-3-60V.
- HVACWork status not resolved
Photograph shows large-diameter pipes or ducts viewed from below, joined by corrugated flexible couplings, with heavy surface oxidation and rust-colored discoloration visible throughout; a rusted metal bracket/hanger is also visible.
- HVACWork status not resolved
the upper portions of the filter media appear darker with dust accumulation while the lower portions show cleaner media
- HVACWork status not resolved
filter media appears moderately loaded with particulate
- HVACWork status not resolved
Photograph shows a close-up of heavily corroded and discolored corrugated metal heat exchanger tubes or coil assembly, with significant rust and oxidation visible across the tube surfaces and surrounding metal components.
- UnclassifiedWork status not resolved
- HVACWork status not resolved
Photograph shows multiple large flexible HVAC ducts with heavy dust and debris accumulation on exterior surfaces, running through a confined space; foil-faced insulation or duct board is visible in the background with apparent deterioration at a connection point.