HVAC Diagnostic and Refrigerant Service — Added R-410A and R-22
- HVAC
On July 8, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 9866 Manchester Road, St. Louis, MO 63119.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$945
Performed a commercial diagnostic service and commercial labor, and added 2 pounds of R-410A refrigerant and 5 pounds of R-22 refrigerant.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an HVAC system, displaying R22 refrigerant readings: low-side 51.3 psig (evaporator saturation 26.8°F) and high-side 232.1 psig (condenser saturation 111.7°F).
- HVACWork status not resolved
Photograph shows a large HVAC condensing unit on a concrete pad with red and blue refrigerant hoses connected to its service ports and a digital manifold gauge set placed on the ground, indicating refrigerant pressure testing or charging in progress.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an HVAC system via refrigerant hoses, displaying low-side pressure of 122.6 psi and high-side pressure of 317.3 psi, with superheat (SH) of 24.4 and subcooling (SC) of 10.6, refrigerant type R410A indicated.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an R-22 refrigerant system, displaying low-side pressure of 73 psi (evaporator saturation -25.1°F) and high-side pressure of 136.8 psi (condenser saturation 76.9°F); the gauge and surrounding equipment appear wet.
- HVACWork status not resolved
Photograph shows a pleated HVAC air filter installed in a return air duct slot; the filter appears white and relatively clean with a handwritten date '2/5/26' on its edge.
- HVACWork status not resolved
Photograph shows a CPS digital refrigerant scale displaying a reading of 2 lbs and 35.0 oz, with water droplets on the device, resting on a gray surface.
- HVACWork status not resolved
Photograph shows a large, heavily soiled fibrous air filter installed in an HVAC air handler, with visible dust and debris loading across the filter media; copper lines and metal unit housing are visible in the lower left.
- HVACWork status not resolved
CKT#1 shows 8.4 lbs R22 and CIRC#1 shows 3.4 lbs refrigerant-22
- HVACWork status not resolved