Record 1Public property record

HVAC Refrigerant Service — Refrigerant charge added (410, 3 lbs max)

  • HVAC

On July 3, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 105 Dunn Road, Florissant, MO 63031.

Record date

Documented details

  • Outcome: Paid in full

Available findings

  • HVACCompleted work$912

    Added refrigerant charge (410, up to 3 lbs max) with after-hours commercial maintenance labor billed at 2.5 hours of 410-A labor.

  • HVACWork status not resolved

    Photograph shows a CPS digital refrigerant scale (model #T6-141) displaying a reading of -2 lbs 6.00 oz, with a coiled cable attached, resting on a light-colored surface.

  • HVACWork status not resolved

    Photograph shows a rooftop HVAC condensing unit with refrigerant service hoses (red and blue) and a digital manifold gauge set connected to service ports; insulated suction and liquid lines run to a secondary air handler unit, with visible frost/ice on the suction line near the condenser; a vacuum pump with yellow hose and technician tool bag with cordless drill are also present.

  • HVACWork status not resolved

    Photograph shows a Testo 557 digital manifold gauge displaying R-410A refrigerant readings: left side shows approximately 40.6°F superheat (SH) and 148.1 psi, right side shows approximately 44°F subcooling (SC) and 413.9 psi.

  • HVACWork status not resolved

    Photograph shows a Testo 557 digital manifold gauge set connected to an HVAC system, displaying R410A refrigerant readings: low-side pressure 155.6 psi with superheat of 24.1°F, and high-side pressure 475.7 psi with subcooling of 9.5°F.

  • HVACWork status not resolved

    Photograph shows a Testo 557 digital manifold gauge connected to an HVAC system, displaying R410A refrigerant readings: low-side 22.3 psig / 21.8°F saturation and high-side 349.2 psig / 128.6°F saturation.

  • HVACWork status not resolved

    the thermostat housing and surrounding wall show visible dirt and grime accumulation

  • HVACWork status not resolved

    a second note requests keeping heat/cool at a comfortable level for occupants and merchandise

  • HVACWork status not resolved
  • HVACWork status not resolved

    Photograph shows a Testo 557 digital manifold gauge displaying R410A refrigerant readings: T1 = 92.6°F, T2 = 115.4°F, high-side pressure = 148.8 psi, low-side pressure = 41.25 psi.

Record 2Public property record

HVAC Service Invoice — No-charge HVAC service visit

  • HVAC

On July 3, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 105 Dunn Road, Florissant, MO 63031.

Record date

Available findings

  • HVACCompleted work
  • HVACWork status not resolved

    Photograph shows a yellow SPK2 handheld digital thermometer with its probe inserted into a light-colored metal panel (consistent with an HVAC unit casing), displaying a reading of 78.6°F.

  • HVACWork status not resolved

    Photograph shows a handheld SPK2 digital thermometer displaying a reading of 63.5°F, held against what appears to be an HVAC unit or metal panel surface with dark staining visible along a seam in the background.

Record 3Public property record

HVAC Diagnostic Service — Commercial diagnostic, labor

  • HVAC

On July 7, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 105 Dunn Road, Florissant, MO 63031.

Record date

Documented details

  • Outcome: Paid in full

Available findings

  • HVACCompleted work$759

    Commercial HVAC diagnostic service and return trip performed with 2 hours of commercial labor, and 404-A refrigerant supplied.

  • HVACWork status not resolved

    Photograph shows a blue HVAC/refrigeration control board mounted in a metal enclosure, with an illuminated red LED display (possibly showing an error or status code), multiple wired terminal connections, a capacitor, and labeled inputs for room temp, defrost temp, suction temp, suction pressure, and outdoor temp.

  • HVACWork status not resolved

    Photograph shows an HVAC coil (condenser or evaporator) with fins heavily coated in dust, dirt, and debris accumulation across the entire visible surface, indicating significant restriction to airflow.

  • HVACWork status not resolved

    Photograph shows the condenser coil fins of an outdoor HVAC unit heavily fouled with accumulated dirt, dust, and debris across the entire coil surface, with the unit mounted on metal support rails above a concrete pad.

  • HVACWork status not resolved

    Photograph shows multiple electrical cables routed across a flat roof membrane, converging at a heavily corroded/tar-coated conduit stub with a deteriorated weatherproof connector and a cable clamp; visible corrosion and rust are present on the fittings.

  • HVACWork status not resolved
  • UnclassifiedWork status not resolved

    Photograph shows a storage room interior with metal shelving, red plastic baskets, cardboard boxes, a vertical black pipe along the wall, and a missing/displaced ceiling tile revealing a dark open void above; a handwritten sign reading 'Please Not open' is visible on a wall panel or door.

View 105 Dunn Road, Florissant, MO 63031 on Fresh House