HVAC Refrigerant Service — Refrigerant charge added (410, 3 lbs max)
- HVAC
On July 3, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 105 Dunn Road, Florissant, MO 63031.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$912
Added refrigerant charge (410, up to 3 lbs max) with after-hours commercial maintenance labor billed at 2.5 hours of 410-A labor.
- HVACWork status not resolved
Photograph shows a CPS digital refrigerant scale (model #T6-141) displaying a reading of -2 lbs 6.00 oz, with a coiled cable attached, resting on a light-colored surface.
- HVACWork status not resolved
Photograph shows a rooftop HVAC condensing unit with refrigerant service hoses (red and blue) and a digital manifold gauge set connected to service ports; insulated suction and liquid lines run to a secondary air handler unit, with visible frost/ice on the suction line near the condenser; a vacuum pump with yellow hose and technician tool bag with cordless drill are also present.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge displaying R-410A refrigerant readings: left side shows approximately 40.6°F superheat (SH) and 148.1 psi, right side shows approximately 44°F subcooling (SC) and 413.9 psi.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge set connected to an HVAC system, displaying R410A refrigerant readings: low-side pressure 155.6 psi with superheat of 24.1°F, and high-side pressure 475.7 psi with subcooling of 9.5°F.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an HVAC system, displaying R410A refrigerant readings: low-side 22.3 psig / 21.8°F saturation and high-side 349.2 psig / 128.6°F saturation.
- HVACWork status not resolved
the thermostat housing and surrounding wall show visible dirt and grime accumulation
- HVACWork status not resolved
a second note requests keeping heat/cool at a comfortable level for occupants and merchandise
- HVACWork status not resolved
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge displaying R410A refrigerant readings: T1 = 92.6°F, T2 = 115.4°F, high-side pressure = 148.8 psi, low-side pressure = 41.25 psi.