HVACCompleted work
Heating maintenance performed under the Commercial Maintenance Plan.
HVACWork status not resolved
Photograph shows a packaged gas unit data plate with model number TGA090S2BM1Y (A6206) and serial number 5606G13455, along with a control box parts arrangement diagram for a 090-150 Packaged Gas Unit; handwritten markings '3' and '56x5' are visible in blue marker.
HVACWork status not resolved
Fieldpiece refrigerant-side diagnostic for circuit 1 shows R-22 refrigerant with suction pressure 55.4 psig, liquid pressure 147.1 psig, actual superheat 31.0°F (elevated), and actual subcooling 4.8°F (low), indicating a possible undercharge condition.
HVACWork status not resolved
filters appear heavily loaded with dust and debris, with a handwritten date '03/05/24' visible on the filter frame
HVACWork status not resolved
Photograph shows Fieldpiece app refrigerant-side measurements for circuit 2: suction pressure 60.5 psig, liquid pressure 163.2 psig, actual superheat 31.7°F, actual subcooling 6.2°F, refrigerant type R-22.
HVACWork status not resolved
Photograph shows multiple heat exchanger tubes with severe rust, corrosion, and debris accumulation; surrounding metal housing also exhibits heavy oxidation and rust streaking.
HVACWork status not resolved
Photograph shows a commercial rooftop package HVAC unit with access panels open, exposing the compressor, blower motor, condenser coil, and heat exchanger/burner section; the mounting curb exhibits significant rust and corrosion, and a wiring diagram is visible mounted inside the unit panel.
HVACWork status not resolved
HVACWork status not resolved
Photograph shows two large insulated pipes running parallel with visible rust-brown staining and corrosion spotting across their white outer surfaces; a hand is visible touching the smaller pipe.