- HVAC · Rooftop packaged gas unit received heating maintenance · Oct 2026
- HVAC · Refrigerant diagnostic found possible undercharge on circuit 1 (R-22 system) · 2026
- HVAC · Rooftop unit panels open; heat exchanger surfaces show heavy surface oxidation · 2026
RECORD SUMMARY
Fresh House preserves inspections, repairs, and appraisals so a home's history is never lost.
This page contains 2 documented records for 15367 Manchester Road, Ballwin, MO 63011, dated from September 2026 through October 2026.
HVAC Service Invoice — No-charge service visit
- HVAC
Built from Housecall Pro data
- HVACno service lines or work details are listed
Only original contributor can modify this entry
Create an account to manage your contributions over time
HVAC Heating Maintenance — Heating maintenance, maintenance plan
- HVAC
Built from Housecall Pro data
- HVACHeating maintenance performed under the Commercial Maintenance Plan.
- HVACPhotograph shows a packaged gas unit data plate with model number TGA090S2BM1Y (A6206) and serial number 5606G13455, along with a control box parts arrangement diagram for a 090-150 Packaged Gas Unit; handwritten markings '3' and '56x5' are visible in blue marker.
- HVACFieldpiece refrigerant-side diagnostic for circuit 1 shows R-22 refrigerant with suction pressure 55.4 psig, liquid pressure 147.1 psig, actual superheat 31.0°F (elevated), and actual subcooling 4.8°F (low), indicating a possible undercharge condition.
- HVACfilters appear heavily loaded with dust and debris, with a handwritten date '03/05/24' visible on the filter frame
- HVACPhotograph shows Fieldpiece app refrigerant-side measurements for circuit 2: suction pressure 60.5 psig, liquid pressure 163.2 psig, actual superheat 31.7°F, actual subcooling 6.2°F, refrigerant type R-22.
- HVACPhotograph shows multiple heat exchanger tubes with severe rust, corrosion, and debris accumulation; surrounding metal housing also exhibits heavy oxidation and rust streaking.
- HVACPhotograph shows a commercial rooftop package HVAC unit with access panels open, exposing the compressor, blower motor, condenser coil, and heat exchanger/burner section; the mounting curb exhibits significant rust and corrosion, and a wiring diagram is visible mounted inside the unit panel.
- HVACPhotograph shows two large insulated pipes running parallel with visible rust-brown staining and corrosion spotting across their white outer surfaces; a hand is visible touching the smaller pipe.