HVAC Thermostat Installation — Non-programmable thermostat installed
- HVAC
On July 16, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 1980 Centurion Drive, Fenton, MO 63026.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$349
Performed a residential diagnostic service and installed a non-programmable thermostat.
- HVACWork status not resolved
Photograph shows the interior of a furnace with multiple heavily dust-coated and discolored wiring bundles zip-tied together, visible active blue burner flames in the background, and significant rust and debris accumulation on metal components.
- HVACWork status not resolved
fan is set to Auto and mode is set to Cool
- HVACWork status not resolved
Fieldpiece app shows live R-410A refrigerant measurements: suction pressure 141.0 psig, liquid pressure 346.4 psig, actual superheat 17.2°F, actual subcooling 13.9°F, and Delta T 17.7°F.
- HVACWork status not resolved
Fieldpiece app air-side measurements show return dry bulb 82.1°F / wet bulb 71.7°F / RH 60.5% and supply dry bulb 64.5°F / wet bulb 61.4°F / RH 84.1%, with a Delta T of 17.6°F; system capacity reading is blank.