Hi, I'm 2126 Meadow Drive. I only speak from this property's source-backed records — 1 document from 1 contributor. If there's no record, I'll tell you I don't know rather than guess. Every claim links to its source.
2126 Meadow Drive
Across 1 record on this home
Completed work
Invoices and paid receipts
Estimated · not confirmed
Quotes, estimates, and other amounts not confirmed as performed
Property History Report
Negotiate this home like you've seen its receipts. You have.
Free right now · built from this home's 1 documented records
Fresh House Property Summary
Highlights selected from 1 documented record for this property.
- HVAC · AC condenser fan motor and capacitor serviced · Aug 2026
- HVAC · AC diagnostic performed after no-cooling complaint at 85°F indoors · 2026
- HVAC · Post-service refrigerant readings showed supply air near target temperature · 2026
RECORD SUMMARY
Fresh House preserves inspections, repairs, and appraisals so a home's history is never lost.
This page contains 1 documented record for 2126 Meadow Drive, Barnhart, MO 63012. The amount summary includes $554 in completed work across HVAC; appraisal values and permit-declared valuations are excluded.
HVAC Condenser Fan Motor Service — Condenser fan motor service
- HVAC
Built from Housecall Pro data
- $554HVACPerformed a residential diagnostic service and a condenser fan motor service, including capacitor.
- HVACPhotograph shows an outdoor HVAC condenser unit with the electrical access panel open, exposing a run capacitor, contactor, and associated wiring; multiple service tools are present on and around the unit, indicating active service work in progress.
- HVACFieldpiece app diagnostic shows R-410A system with suction pressure 146.9 psig, liquid pressure 280.3 psig, actual superheat 17.4°F, actual subcooling 4.3°F, and supply air dry bulb 58.5°F close to target 58.9°F indicating adequate evaporator performance.
- HVACPhotograph shows Fieldpiece app screen with live HVAC measurements: return dry bulb 76.6°F, supply dry bulb 58.6°F, Delta T 18.0°F, suction pressure 145.9 psig, liquid pressure 279.4 psig, and supply relative humidity 85.6%.
- HVACFieldpiece live refrigerant measurements show R-410A system with suction pressure 138.4 psig, liquid pressure 255.7 psig, actual superheat 24.9°F, actual subcooling 4.7°F, and Delta T 16.8°F.
- HVACFieldpiece app air-side measurements show return dry bulb 76.2°F / wet bulb 65.1°F / RH 54.8% and supply dry bulb 58.0°F / wet bulb 56.5°F / RH 90.9%, with a Delta T of 18.2°F; system capacity reading is unavailable (--).
- HVACFieldpiece air-side and refrigerant diagnostics show supply dry bulb (58.5°F) close to target (58.9°F) indicating adequate airflow, and actual superheat close to target superheat (19.2°F) indicating adequate refrigerant charge for a fixed metering device using a standard superheat table; outdoor dry bulb is 76.6°F.
- HVACMaintenance meld logged for no air conditioning with indoor temperature reported over 85°F
- HVACPhotograph shows an outdoor HVAC condenser unit viewed from above with the fan motor wiring disconnected and loose colored wires (red, yellow, green) visible at the motor hub; a Fluke clamp meter and red-handled pliers are resting on the fan guard, indicating active service or diagnostic work in progress.
HVAC
HVAC
HVAC
HVACOnly original contributor can modify this entry
Create an account to manage your contributions over time
Only the original contributor can modify this entry · Create an account to manage your contributions over time.