HVAC Condenser Fan Motor Service — Condenser fan motor service
- HVAC
On August 28, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 2126 Meadow Drive, Barnhart, MO 63012.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$554
Performed a residential diagnostic service and a condenser fan motor service, including capacitor.
- HVACWork status not resolved
Photograph shows an outdoor HVAC condenser unit with the electrical access panel open, exposing a run capacitor, contactor, and associated wiring; multiple service tools are present on and around the unit, indicating active service work in progress.
- HVACWork status not resolved
Fieldpiece app diagnostic shows R-410A system with suction pressure 146.9 psig, liquid pressure 280.3 psig, actual superheat 17.4°F, actual subcooling 4.3°F, and supply air dry bulb 58.5°F close to target 58.9°F indicating adequate evaporator performance.
- HVACWork status not resolved
Photograph shows Fieldpiece app screen with live HVAC measurements: return dry bulb 76.6°F, supply dry bulb 58.6°F, Delta T 18.0°F, suction pressure 145.9 psig, liquid pressure 279.4 psig, and supply relative humidity 85.6%.
- HVACWork status not resolved
Fieldpiece live refrigerant measurements show R-410A system with suction pressure 138.4 psig, liquid pressure 255.7 psig, actual superheat 24.9°F, actual subcooling 4.7°F, and Delta T 16.8°F.
- HVACWork status not resolved
Fieldpiece app air-side measurements show return dry bulb 76.2°F / wet bulb 65.1°F / RH 54.8% and supply dry bulb 58.0°F / wet bulb 56.5°F / RH 90.9%, with a Delta T of 18.2°F; system capacity reading is unavailable (--).
- HVACWork status not resolved
Fieldpiece air-side and refrigerant diagnostics show supply dry bulb (58.5°F) close to target (58.9°F) indicating adequate airflow, and actual superheat close to target superheat (19.2°F) indicating adequate refrigerant charge for a fixed metering device using a standard superheat table; outdoor dry bulb is 76.6°F.
- HVACWork status not resolved
Maintenance meld logged for no air conditioning with indoor temperature reported over 85°F
- HVACWork status not resolved
Photograph shows an outdoor HVAC condenser unit viewed from above with the fan motor wiring disconnected and loose colored wires (red, yellow, green) visible at the motor hub; a Fluke clamp meter and red-handled pliers are resting on the fan guard, indicating active service or diagnostic work in progress.
- HVACWork status not resolved