HVAC Refrigerant Recharge — R-22 refrigerant added to HVAC system
- HVAC
On August 4, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 301 Oriole Drive, St. Charles, MO 63301.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$1,200
Charged the HVAC system with R-22 refrigerant (6.5 lb billed) and a trip fee was applied.
- HVACWork status not resolved
Photograph shows Fieldpiece app HVAC air-side measurements: Return dry bulb 76.2°F / wet bulb 67.2°F / RH 62.7% / dew point 62.5°F / enthalpy 31.7 Btu/lbm; Supply dry bulb 73.1°F / wet bulb 66.1°F / RH 69.1% / dew point 62.3°F / enthalpy 30.8 Btu/lbm; Delta T 3.1°F; Refrigerant side suction pressure 74.4 psig and liquid pressure 251.1 psig.
- HVACWork status not resolved
Fieldpiece app measurements show R-22 refrigerant system with suction pressure 74.3 psig, liquid pressure 245.0 psig, actual superheat 15.3°F, and actual subcooling 12.7°F; air side diagnostics show no dry bulb readings.
- HVACWork status not resolved
Fieldpiece diagnostic app shows R-22 system with suction pressure 74.3 psig, liquid pressure 251.0 psig, actual superheat 16.8°F, actual subcooling 14.8°F; air side diagnostics indicate supply air dry bulb (73.1°F) is above target evaporator exit dry bulb (60.3°F), which usually indicates low capacity.
- HVACWork status not resolved
Photograph shows a Yellow Jacket digital gauge displaying a reading of -9.37, resting on bare soil outdoors alongside a blue tool or hose.
- HVACWork status not resolved
- HVACWork status not resolved
gas supply pipes are visible at the base of the unit, and debris/dust accumulation is visible around the flue collar at the top of the furnace