Complete public upload archive

Property records for 3212 Laclede Station Road, Maplewood, MO 63143

All 2 public upload records returned by the Fresh House property feed are available across 1 server-rendered page. This page shows records 1 to 2.

Record details are source-backed where available. Permit status and descriptions repeat the publishing agency's data; they do not independently establish that work was completed.

Return to the property overview
Record 1Public property record

HVAC Service Invoice — No-charge HVAC service visit

  • HVAC

On September 22, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 3212 Laclede Station Road, Maplewood, MO 63143.

Record date

Available findings

  • HVACCompleted work
Record 2Public property record

HVAC Service Invoice — No-charge HVAC service visit

  • HVAC

On October 27, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 3212 Laclede Station Road, Maplewood, MO 63143.

Record date

Available findings

  • HVACCompleted work
  • HVACWork status not resolved

    Photograph shows large looping heat exchanger tubes or coils with visible rust, orange-brown corrosion at bends and seams, surface staining on the white coating, and a corroded metal pipe visible in the background interior of the unit.

  • HVACWork status not resolved

    Photograph shows a Fluke 323 True RMS Clamp Meter with the rotary dial set to OFF and the LCD display showing approximately '5', being held near metal equipment.

  • HVACWork status not resolved

    a handwritten date reading '10/22/26' is visible on the filter frame

  • HVACWork status not resolved

    Fieldpiece app refrigerant side measurements for R-410A system: suction pressure 126.6 psig, liquid pressure 302.4 psig, suction temp 48.4°F, liquid temp 79.4°F, vapor saturation 43.5°F, liquid saturation 96.4°F, actual superheat 4.9°F, actual subcooling 17.0°F, discharge pressure 302.4 psig.

  • HVACWork status not resolved

    Photograph shows furnace heat exchanger tubes with heavy surface rust, orange-brown corrosion staining, and visible cracking or splitting at the tube seams, indicating significant deterioration of the heat exchanger.

  • HVACWork status not resolved
  • HVACWork status not resolved

    Photograph shows Fieldpiece app screen displaying live R-410A refrigerant measurements: suction pressure 130.1 psig, suction temperature 47.0°F, actual superheat 2.1°F; liquid pressure 320.0 psig, liquid temperature 84.5°F, actual subcooling 15.8°F, discharge pressure 320.0 psig.

View 3212 Laclede Station Road, Maplewood, MO 63143 on Fresh House