HVACCompleted work
HVACWork status not resolved
Photograph shows a Fluke 323 True RMS Clamp Meter reading 17.8 AAC, being used to measure current draw at what appears to be an outdoor HVAC condenser unit with visible wiring and refrigerant lines in the background.
HVACWork status not resolved
Fieldpiece app measurements show air-side Delta T of 13.9°F (return dry bulb 71.3°F, supply dry bulb 57.4°F), return RH 63.7%, supply RH 84.6%, and refrigerant-side suction pressure 60.1 psig / liquid pressure 250.6 psig.
HVACWork status not resolved
Photograph shows a mobile HVAC diagnostic app screen displaying air-side measurements: return dry bulb 71.4°F, supply dry bulb 57.4°F, Delta T 14.0°F; return RH 63.7%, supply RH 84.6%; Btu capacity field is blank. Refrigerant side section is partially visible but cut off.
HVACWork status not resolved
Fieldpiece app diagnostic shows R-22 system with suction pressure 59.5 psig, actual superheat 32.9°F (elevated), liquid pressure 251.9 psig, actual subcooling 8.4°F, and air-side dry bulb 57.5°F near target 54.8°F indicating adequate evaporator airflow.
HVACWork status not resolved
Photograph shows an electrical contactor or relay block (terminals labeled 21 and 23) with multiple wires heavily coated in dust, lint, and cobwebs, indicating significant accumulation and lack of maintenance.
HVACWork status not resolved
HVACWork status not resolved
Photograph shows the manufacturer data plate on an outdoor central cooling air conditioner: Model 38CKC048300, Serial 1600E23580, factory charged with R-22 (6.63 lbs), 208-230V/1PH/60Hz power supply, 24.4A RLA compressor, 1/4 HP fan motor, min circuit amps 31.9, max fuse 50A.