HVAC Leak Search — Diagnostic and 1-hour refrigerant leak search
- HVAC
On June 16, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 3600 North Lindbergh Boulevard, St. Ann, MO 63074.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$300
Performed a commercial diagnostic service and a one-hour refrigerant leak search on the HVAC system.
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an HVAC system, displaying R410A refrigerant with a low-side pressure of 130.8 psi, high-side pressure of 339.2 psi, and subcooling (SC) of 10.4°F; superheat (SH) reading is dashed/unavailable.
- HVACWork status not resolved
Photograph shows an HVAC control board (part no. 25-2899-94, REV. K, RY11943) with a small LCD display indicating a maintenance alert message, multiple wiring harnesses connected, and visible dust accumulation on the board.
- HVACWork status not resolved
Photograph shows an evaporator coil assembly with a large bundle of coiled copper refrigerant tubing, a thermostatic expansion valve (TXV) with brass body and gray sensing bulb, and aluminum fin coil face; copper lines show age-related oxidation patina.
- HVACWork status not resolved
model ZF180N30B2A1AAA1A1, serial N2A0541255, rated 300,000 BTU/HR total input, factory charged with R410A, 208/230–3–60V
- HVACWork status not resolved
Photograph shows a Testo 557 digital manifold gauge connected to an outdoor HVAC unit, displaying R410A refrigerant pressures of 94.3 psi (SH side) and 94.9 psi (SC side).