Record 1Public property record

HVAC Maintenance Plan Visit — Maintenance plan visit #1

  • HVAC

On April 15, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 4 Chestnut Circle, Florissant, MO 63033.

Record date

Available findings

  • HVACCompleted work

    Visit #1 under the Residential Maintenance Plan was performed at 4 Chestnut Circle.

  • HVACWork status not resolved

    liquid pressure 250.8 psig, liquid temp 67.8°F, liquid saturation 83.7°F, actual subcooling 15.9°F, discharge pressure 117.4 psig

  • HVACWork status not resolved
Record 2Public property record

HVAC Maintenance Plan Visit — Maintenance plan visit #2

  • HVAC

On October 8, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 4 Chestnut Circle, Florissant, MO 63033.

Record date

Available findings

  • HVACCompleted work

    Visit #2 of the Residential Maintenance Plan was performed at the property.

  • HVACWork status not resolved

    TUD2B080ACV32BA, Serial No. 18173NKA1G, manufactured April 2018, rated at 80,000 BTU/HR high input and 52,000 BTU/HR low input

  • HVACWork status not resolved

    a borescope inspection camera, drill, and other tools are visible on the floor nearby, and replacement air filters are leaning against the wall to the right

  • HVACWork status not resolved

    Photograph shows the interior of an open furnace with a green control board (Honeywell software label visible), a small LCD display module reading 'TUD2B080ACV32BA / 18173NKA1G', and multiple multi-colored wiring harnesses connected to the board.

  • HVACWork status not resolved

    Photograph shows a Fluke 323 True RMS Clamp Meter clamped around wiring at an HVAC unit, displaying a reading of 6.9 AAC (AC amperes).

  • HVACWork status not resolved

    Photograph shows the interior of a gas furnace with access panels removed, revealing the heat exchanger/burner assembly in the upper section and the control board with LCD display, wiring harnesses, and terminal strips in the lower compartment.

  • HVACWork status not resolved

    Photograph shows a Fluke 323 True RMS Clamp Meter displaying a reading of 46 AAC (AC amperes).

  • HVACWork status not resolved

    Photograph shows a wall-mounted digital touchscreen thermostat displaying a current indoor temperature of 75°F, indoor humidity of 59%, system status of 'System Off,' fan mode set to Auto, and a Runtime History bar chart.

  • HVACWork status not resolved