HVAC Compressor Replacement — HVAC compressor replaced
- HVAC
On August 20, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 4338 Ventura Place Drive, St. Louis, MO 63128.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$3,310
Replaced compressor with a new unit in the HVAC system.
- HVACWork status not resolved
Photograph shows a Fieldpiece app screen displaying live refrigerant measurements for an R-410A system: suction pressure 112.0 psig, suction temperature 49.7°F, actual superheat 12.7°F, liquid pressure 322.0 psig, liquid temperature 98.6°F, actual subcooling 2.1°F, and discharge pressure 322.0 psig.
- HVACWork status not resolved
Fieldpiece app refrigerant-side measurements show R-410A system with suction pressure 130.5 psig, suction temperature 55.4°F, actual superheat 10.4°F, liquid pressure 319.2 psig, liquid temperature 97.7°F, actual subcooling 2.4°F, and discharge pressure 319.2 psig; air-side diagnostics show no connected tools.
- HVACWork status not resolved
Photograph shows a Fluke 323 True RMS Clamp Meter displaying a reading of 0.4 A AC, with the rotary dial set to the amperes position, being used near outdoor wiring.
- HVACWork status not resolved
Photograph shows a scroll compressor with model ZP21LXE-PFV-800 and serial 26G101A7M installed inside an outdoor condenser unit, with a technician partially visible in the background.
- HVACWork status not resolved