HVAC Diagnostic Service — Commercial diagnostic service
- HVAC
On July 27, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 538 Rudder Road, Fenton, MO 63026.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$320
Performed commercial diagnostic service with commercial labor and supplied two 16/25/1 Merv 7 pleated filters.
- HVACWork status not resolved
Photograph shows two ProPleat MERV 10, 16x20x2 pleated air filters installed side-by-side in an HVAC filter rack; surrounding housing shows dust/debris accumulation along the top edge.
- HVACWork status not resolved
Photograph shows the base corner of a large white HVAC unit with significant rust and orange-brown staining along the bottom panel edges and around a black elbow condensate drain pipe, with visible deterioration of the surrounding roofing membrane.
- HVACWork status not resolved
Photograph shows a rooftop HVAC unit with condenser coil fins heavily fouled with dirt and debris deposits across the entire coil face; fan grille shows rust discoloration and unit cabinet has surface rust at fastener points.
- HVACWork status not resolved
Photograph shows a rooftop condenser unit with the condenser coil face heavily fouled with white/gray debris, dirt, and scale buildup across the entire coil surface; rust/corrosion is visible at the base of the coil panel, and a disconnect box with ON/OFF switch is mounted on the right side of the unit.
- HVACWork status not resolved
Photograph shows a 3-pole electrical contactor mounted inside an enclosure, with red insulated wires connected to the upper terminals and yellow-tipped wires at the lower terminals; additional red, yellow, and gray conductors are visible in the surrounding area.
- HVACWork status not resolved
the label is heavily soiled and partially peeling
- HVACWork status not resolved
Photograph shows Fieldpiece app air-side measurements: return dry bulb 79.3°F / wet bulb 68.8°F / RH 58.5% / dew point 63.4°F / enthalpy 32.9 Btu/lbm; supply dry bulb 62.4°F / wet bulb 59.9°F / RH 86.4% / dew point 58.3°F / enthalpy 26.3 Btu/lbm; Delta T 16.9°F; refrigerant side suction and liquid pressures not linked.
- HVACWork status not resolved
Photograph shows a 3-pole electrical contactor with yellow-insulated wire lugs connecting multiple red conductors on both the line and load sides, housed within an electrical enclosure
- HVACWork status not resolved
Fieldpiece app psychrometric measurements show return air dry bulb 79.3°F, wet bulb 68.7°F, RH 58.5%, enthalpy 32.9 Btu/lbm and supply air dry bulb 62.5°F, wet bulb 59.9°F, RH 86.4%, enthalpy 26.4 Btu/lbm, with a Delta T of 16.8°F.
- HVACWork status not resolved
- HVACWork status not resolved
Photograph shows three HVAC air filters with cardboard frames laid on a concrete surface; all three filter media panels are heavily darkened with accumulated dust and debris, indicating significant soiling and likely need for replacement.