HVAC Service Call — Commercial trip fee and labor
- HVAC
On August 14, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 6255 Ronald Reagan Drive, Lake St. Louis, MO 63367.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$260
Commercial trip fee and commercial labor were performed at the service address.
- HVACWork status not resolved
Photograph shows the lower exterior of a package/rooftop HVAC unit with visible rust and corrosion along the base pan, an open rectangular drain slot in the base, a circular drain cap/plug, accumulated debris (leaves and dirt) at the unit's base, and an open access panel on the right side exposing internal refrigerant lines.
- HVACWork status not resolved
Photograph shows HVAC refrigerant diagnostic app displaying R-410A system readings: suction pressure 144.0 psig / 59.4°F, vapor saturation 50.5°F, actual superheat 8.9°F; liquid pressure 369.3 psig / 103.5°F, liquid saturation 110.5°F, actual subcooling 7.0°F, discharge pressure 369.3 psig; air side dry bulb 62.0°F, target dry bulb 62.1°F.
- HVACWork status not resolved
Fieldpiece app refrigerant-side measurements show R-22 system with suction pressure 66.6 psig, liquid pressure 327.6 psig, actual superheat 29.6°F, actual subcooling 39.1°F, and air-side dry bulb 64.9°F.
- HVACWork status not resolved
Photograph shows a cylindrical tank or pipe surface with extensive cracking and crazing of the outer coating, and heavy dark black spotting concentrated at the top seam/joint area, with additional scattered spotting across the surface.
- HVACWork status not resolved
Photograph shows a Fluke 323 True RMS Clamp Meter displaying approximately 53 amps AC, being used to measure current on electrical wiring near sheet-metal equipment.
- HVACWork status not resolved
Fieldpiece app refrigerant side measurements show R-410A with suction pressure 140.2 psig, liquid pressure 309.4 psig, actual superheat 12.5°F, actual subcooling 9.6°F; air side diagnostics indicate supply dry bulb (63.0°F) is close to target dry bulb (63.1°F), indicating adequate evaporator performance.