On June 11, 2026, JLM HEATING AND AIR CONDITIONING documented HVAC at 7309 Brunswick Avenue, St. Louis, MO 63119.
- Record date
Documented details
- Outcome: Paid in full
Available findings
- HVACCompleted work$284
Performed a residential diagnostic service and 1.5 hours of labor at the service address.
- HVACWork status not resolved
Photograph shows the interior of a furnace cabinet with a green control board labeled 'SOFTWARE ID PC 0180-0650 V02' and thermostat terminal connections (W, R, G, B/C, Y/Y1) with multiple colored wires bundled and routed to the terminal strip.
- HVACWork status not resolved
Fieldpiece app refrigerant side measurements show R-410A with suction pressure 103.6 psig, liquid pressure 407.5 psig, actual superheat 1.5°F, and actual subcooling 3.3°F; air side diagnostics show no data connected.
- HVACWork status not resolved
Photograph shows an outdoor air conditioning condenser unit with a louvered metal cabinet, mounted on a concrete pad (embossed '30 X 30 X 2'); grass and weeds are visible around the base of the unit.
- HVACWork status not resolved
Photograph shows an outdoor air conditioning condenser unit with louvered side panels heavily fouled with dirt, grass clippings, and organic debris, substantially obstructing airflow through the coil fins; unit sits on a concrete pad surrounded by vegetation.
- HVACWork status not resolved
Fieldpiece refrigerant side measurements for R-410A show suction pressure 115.5 psig, discharge pressure 349.4 psig, actual superheat 22.2°F, and actual subcooling 1.9°F; app warns that highlighted values are outside the normal operating range.
- HVACWork status not resolved
Fieldpiece app refrigerant side measurements show R-410A with suction pressure 103.7 psig (vapor saturation 33.2°F) and liquid pressure 407.1 psig (liquid saturation 117.7°F); actual superheat and subcooling are not displayed (link tool not connected for temperature probes).
- HVACWork status not resolved
Photograph shows galvanized round ductwork with a wye branch fitting, loose multi-colored electrical wires running alongside the ducts, and a handheld instrument (yellow/green) resting on a flat duct surface in what appears to be a basement or utility area.
- HVACWork status not resolved
- HVACWork status not resolved
Photograph shows the exterior louvered panel of an outdoor HVAC unit with heavy dirt and debris accumulation on the vents; a power drill is visible nearby suggesting active service work.