Home Inspection is listed on Greensmith Home Inspection LLC's current Fresh House business profile. It is not inferred from property records and is not presented here as completed work.
HOME INSPECTOR

Greensmith Home Inspection LLC
AREAS OF EXPERTISE
4 servicesProfile-listed services
Full service & record summaryPROPERTY RECORDS
What this professional has documented.
Structured findings below are extracted from the documented professional records shown on this page.
20 property records shown.
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property found generally good condition with no structural issues; four deficiencies noted — low attic insulation, unsecured basement handrail, nearly dead smoke detector battery, and unplugged refrigerator.
- ElectricalBasement smoke detector battery is almost completely dead and replacement is recommended remaining smoke detectors functioned properly 2-prong ungrounded outlets present throughout interior
- FoundationBasement handrail is not secure and needs a middle bracket installed; attic insulation is low (should rise above rafters) and additional blown-in fiberglass insulation is recommended; perimeter insulation not visible; no moisture detected and poured concrete foundation is satisfactory.
- RoofArchitectural shingle gable roof estimated 10–12 years old is installed correctly and in satisfactory condition; flashings, gutters, soffit, fascia, and ventilation all satisfactory; no skylights present.
- HVACdigital thermostat and metal ducting satisfactory
- Plumbingcopper and PEX supply pipes and PVC waste pipes satisfactory no sump pump present main water shutoff located in basement
- WindowsVinyl exterior windows and double-hung/fixed interior windows are in satisfactory condition.
- Pestno action or treatment recommended

1224 Kilgore Drive
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property found home in generally good condition with no structural issues; deficiencies noted across site, roofing, electrical, HVAC, plumbing, sewer, foundation, windows, and interior systems.
- RoofArchitectural shingle roof estimated 1 year old and installed correctly; one plastic vent pipe flashing is improper and needs correction.
- ElectricalOne family room outlet has hot and neutral wires reversed and needs correction; GFCI outlets are missing at basement laundry and basement bar (within 6 ft of sink); smoke detector absent near basement gas appliances; master bathroom heat lamp switch is faulty and cannot be turned off.
- HVACHVAC information documented.
- Plumbingrear exterior faucet is non-functional and loose from the wall and needs repair
- SewerNo damage observed to sewer lateral lines, but scaling has built up in the cast-iron section reducing pipe diameter and causing water to hold; hydroflushing recommended to remove scaling and restore flow.
- FoundationPreviously repaired exterior foundation cracks are aged and dried and need to be resealed with fresh epoxy; large cracks present in concrete garage floor require repair; repaired basement wall crack appears functional with no moisture intrusion observed.
- WindowsThe window over the kitchen sink has a disconnected crank handle that needs to be reset, preventing the window from closing fully.
- SewerNo structural damage observed to sewer lateral lines; however, scaling has built up and reduced the diameter of the line, and part of the cast-iron section is holding water due to scaling — hydroflushing recommended to remove scaling and restore flow.
- Pestno action or treatment recommended

4974 Brookton Way
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies including end-of-life HVAC, sewer lateral root intrusion, damaged gutter, failed bathroom GFCI, reversed laundry GFCI wiring, loose basement handrail, and missing smoke detectors; no structural issues found.
- FoundationPoured concrete basement foundation is satisfactory with no moisture detected and no deficiencies observed in basement walls; loose handrail on basement stairs needs to be secured.
- HVACvegetation is crowding the AC condenser
- RoofArchitectural shingles estimated 5-10 years old and performing properly; a fallen tree limb damaged the gutter which needs replacement, and the front corner downspout needs reset as it is dumping rain wash onto the roof.
- ElectricalCutler Hammer 100-amp panel is functional; smoke detectors are missing throughout the home, bathroom GFCI outlet is older and will not trip (needs replacement), and laundry GFCI outlet has hot and ground wires reversed; 2-prong ungrounded outlets are present.
- Plumbingcopper supply pipes and PVC waste pipes are satisfactory
- SewerNo damage found to sewer lateral lines, but heavy tree root intrusion and sludge are present; hydroflushing recommended to maintain proper flow and prevent backups.
- SewerSewer lateral inspection found no structural damage to the lateral lines, but heavy tree root intrusion and sludge are present; hydroflushing is recommended to maintain proper flow and prevent backups.
- Pestno action or treatment recommended
1212 Grenshaw Drive
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies including a recalled electrical panel, removed HVAC and plumbing supply systems, basement wall cracks with moisture intrusion, roof flashing and gutter damage, rotted window trim, and signs of interior mildew.
- Electricalbreakers are missing from the panel and smoke detectors are absent throughout the home
- HVACHVAC information documented.
- PlumbingCopper supply waterlines have been removed and the home needs to be re-plumbed
- RoofMetal flashing on one roof vent has lifted allowing moisture entry; soffit and fascia boards are damaged and need repair; a section of rear guttering is damaged and needs replacement; tree limbs overhang the roof and need to be cut back.
- FoundationPoured concrete basement walls have cracks that have allowed moisture infiltration; epoxy sealing is recommended, and the basement moisture condition is noted as musty.
- WindowsSome wood frames and trim around doors and windows have rotted and need to be replaced; the front storm door is out of the frame and the side door frame is also damaged.
- MoldSome interior walls have absorbed moisture, likely from the basement, and show visible signs of mildew growth.
- Pestno treatment recommended

10404 Prince Drive
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property found home in generally good condition with no structural issues; deficiencies noted include aged HVAC (2000/2002), sewer lateral sludge and root intrusion, loose soffit, tree limbs on power lines, missing smoke detectors, attic fan needing replacement, minor ceiling damage in rear bedroom, and one inoperable hallway outlet.
- RoofShingled roof was recently replaced and installed correctly with new architectural shingles; deficiency noted: loose soffit on rear corner of home needs to be secured.
- Electricaldeficiencies include tree limbs pushing on overhead power lines (power company contact recommended), missing smoke detectors throughout home, and one inoperable hallway outlet
- HVACattic fan is operable but too slow to lift slats and likely needs replacement
- Plumbingsewer lateral has sludge buildup in cast-iron portion and tree root intrusion in clay portion, with sludge accumulation damming the line and holding water — hydroflushing recommended
- FoundationPoured concrete basement foundation is satisfactory with no structural issues, no moisture detected, and previous basement wall repairs appeared effective.
- WindowsVinyl exterior windows and double-hung/fixed interior windows are in satisfactory condition.
- Pestno action or treatment recommended

2248 Kerwin Drive
St. Louis, Missouri
Florissant, Missouri
- Home InspectionWhole-home inspection of single-family property found home in generally good condition with no structural issues; deficiencies noted across electrical, HVAC, plumbing, windows, foundation, and pest categories.
- PlumbingBasement laundry sink drains directly into open floor drain (needs proper P-trap and connection to sewer stack); Rheem 40-gallon natural gas water heater (manufactured 2017) functioning properly; main water shutoff needs corrosion removed.
- FoundationUnfinished basement floor has cracks that should be sealed with epoxy; exterior foundation crack should be sealed with urethane caulk; no moisture intrusion observed in basement.
- RoofArchitectural shingle roof estimated 2-5 years old, installed correctly and in satisfactory condition; gable design with metal flashings, aluminum soffit/fascia, and metal gutters all satisfactory.
- HVACGoodman central split system (furnace and 3-ton condenser) manufactured in 2011 is functioning properly but requires annual cleaning and servicing; vegetation crowding the AC condenser must be removed.
- Electrical200-amp Crouse-Hinds panel (aged but performing) with multiple missing GFCI outlets (kitchen, laundry, rear exterior), one inoperable patio outlet, one basement outlet with hot and neutral wires reversed, and two-prong ungrounded outlets present throughout.
- WindowsTwo windows (one in living room, one in master bedroom) have broken seals and need replacement; bedroom window plastic grille is broken and taped; basement window trim cut too close preventing windows from opening — a safety concern.
- PestOlder termite damage observed on a small section of wooden fence in the backyard; no active termite activity found on the rest of the structure; treatment or fence removal recommended.
- SewerSewer lateral lines are open and flowing with no obstructions and no damages observed; lateral lines are PVC from the main stack to the city tie-in.
- PestVisual inspection found older termite damage on the wood fence; no live insects observed; recommendation to spray the affected area with a borate-based solution or remove the damaged fence.
- Radonaverage result was 3.0 pCi/L over 91 hourly intervals, with a minimum of 1.3 pCi/L and maximum of 4.9 pCi/L
2054 Krause Hill Place
Florissant, Missouri
Jennings, Missouri
- PestVisual inspection of SFR and detached garage found no visible evidence of wood destroying insects; no treatment recommended.

2128 Lexa Drive
Jennings, Missouri
St. Peters, Missouri
- Home InspectionWhole-home inspection of condo at 214 Sugar Lake Dr found the property in great condition with no structural issues; deficiencies noted in electrical (Challenger panel, open breaker slot, deck GFCI outlet) and HVAC (annual service needed).
- ElectricalChallenger electric panel (125-amp service) has critical safety flaws — breakers frequently fail to trip during overloads or short circuits — replacement recommended; open breaker slot needs a blank cover installed; rear deck outlet requires replacement with a GFCI-protected outlet.
- HVACAmerican Standard central split system (2.5-ton condenser, manufactured 2017) is performing properly but requires annual cleaning and servicing by a licensed HVAC contractor.
- PlumbingAO Smith 28-gallon electric water heater (manufactured 2017) appears functional; copper supply pipes in satisfactory condition; T&P relief valve present with blow-off leg.
- FoundationSlab-on-grade poured concrete foundation and wood-frame wall structure both observed in satisfactory condition with no deficiencies noted.

214 Sugar Lake Drive
St. Peters, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies including an end-of-life 1974 furnace, sewer line with rootball intrusion and disconnected joint, basement foundation crack with mildew, missing GFCI outlets, 3 broken window panes, and an inoperable exterior faucet; no structural issues noted.
- HVACLennox gas furnace manufactured in 1974 is at end of expected lifespan; Aire Flo 2.5-ton AC condenser manufactured in 2011 was operational but failed to cool the home and requires cleaning and servicing.
- SewerExcessive scaling in cast-iron sewer line with apparent collapsed section, large tree root intrusion forming a rootball, and a disconnected joint at the PVC-to-clay pipe transition separated roughly 2 inches, preventing camera access to the sewer main; hydroflushing recommended.
- PlumbingRear exterior faucet is loose and inoperable; bathtub stuck on shower mode with loose faucet handles; 2008 General Electric 40-gallon natural gas water heater is functional but gas supply shut-off valve has been pressed into the unit rendering it unusable.
- FoundationCrack in basement foundation wall has allowed moisture intrusion resulting in mildew growth; a leaking basement window has rusted the frame and damaged the window seal, contributing to moisture intrusion.
- ElectricalGFCI-protected outlets are absent in the bathroom, kitchen, and basement laundry; one dining-room outlet is inoperable; 2-prong ungrounded outlets are present throughout; 100-amp Murray panel with breakers appears functional.
- RoofArchitectural shingle roof estimated at 10 years old is installed correctly and in satisfactory condition; gutters contain leaves and need cleaning; tree limbs overhang the roof and should be cut back.
- WindowsThree broken window panes require replacement (2 bedroom windows, 1 basement window); many interior windows are painted shut and need to be opened for safety; bathroom window has been taped shut.
- SewerSewer lateral inspection found excessive scaling in cast-iron section, a possible collapsed section or heavy scaling buildup, tree root intrusion forming a large rootball, an offset at the PVC-to-clay pipe transition, and a disconnected joint separated roughly 2" that prevented camera access to the sewer main; hydroflushing recommended.
- PestVisual inspection of SFR/Attached Garage at 1363 Kroeger Drive found no visible evidence of wood destroying insects; no action or treatment recommended.

1363 Kroeger Drive
St. Louis, Missouri
Florissant, MO
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies including a gas-company-flagged range, blocked sewer lateral, excessively rusted 2002 water heater, and a hole in the roof over the garage; no structural deficiencies observed.
- ElectricalGFCI outlet at rear patio is older and will not reset and needs replacement; loose outlet noted in dining room; 2-prong ungrounded outlets present throughout; Murray 200-amp service panel in garage appears functional.
- RoofArchitectural shingle roof estimated 10–15 years old with a hole in the roof over the attached garage requiring repair; remaining shingles are performing properly.
- HVACGoodman central split system (2.5-ton A/C, forced-air furnace) manufactured in 2017 appears satisfactory; furnace could not be tested due to gas shutoff; missing drum panel cover noted; gas kitchen range (Amana) flagged by gas company for inoperable igniter.
- PlumbingKenmore gas water heater manufactured in 2002 is excessively rusted and needs replacement; copper supply pipes satisfactory; property is winterized with no water service active at time of inspection.
- SewerSewer lateral videoscope performed; buildup and debris have reduced the interior diameter to the point where the camera could not reach the city main — sewer lines need to be cabled/cleared then re-camera'd.
- FoundationSlab-on-grade poured concrete foundation and wood-frame wall structure both observed in satisfactory condition with no structural deficiencies noted.

505 Ridge Drive
Florissant, MO
St. Louis, Missouri
- HVACGas appliance inspection found flue venting too close to combustible materials (single-wall requires 6" clearance, double-wall requires 1" clearance), missing TPRV discharge pipe on water heater, condenser not level, and rusty capacitor on addition condenser; gas pressure test and combustion analyzer test both passed; no major concerns noted.
- PestVisual inspection of 9505 Margo Ann Lane found no visible evidence of wood destroying insects (termites, carpenter ants, carpenter bees, or reinfesting wood boring beetles); no treatment recommended.

9505 Margo Ann Lane
St. Louis, Missouri
Wentzville, Missouri
- PestVisual inspection of 87 Cimarron Summit Way found no visible evidence of wood destroying insects (termites, carpenter ants, carpenter bees, or wood boring beetles); no treatment recommended.

87 Cimarron Summit Way
Wentzville, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of two-family building at 3243 Delor St found the property in generally good condition with no structural issues; six deficiencies identified across roofing, HVAC, plumbing, and mold.
- RoofTPO roofing estimated 1-2 years old and in great shape; deficiency noted — soffit damage on the front corner of the building requires repair.
- HVACUnit #1 has a 1998 York gas furnace (92,000 BTU) that has hit the end of expected life; Unit #2 has a 2019 Comfortmaker gas furnace (66,000 BTU), but the central AC is inoperable per the occupant — 3 AC condensers on roof (2 older, 1 newer), and the occupant relies on window units; missing dryer exhaust vents also noted in Unit #2 laundry.
- ElectricalBoth Unit #1 and Unit #2 have Eaton 100-amp service panels with breakers located in the basement; smoke detectors present in both units.
- PlumbingUnit #2 bathroom sink has an active plumbing leak that has persisted for months despite a report to property management; both basement laundry hookups drain into the laundry sink (improperly plumbed) and the laundry sink faucet is inoperable; both units have 2018 Rheem 40-gallon electric water heaters.
- FoundationBasement foundation of stone construction with wood-framed floors and masonry wall structure; no structural issues detected.
- MoldMildew has formed inside the bathroom sink cabinet in Unit #2 as a result of the ongoing plumbing leak under the sink.
- SewerNo damages or obstructions were observed to the sewer lateral lines.
- SewerSewer lateral inspection found lines open and flowing with no visible damage; lines are PVC all the way to the city's main connection.

3243 Delor Street
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property found the home generally in good condition with no structural issues; deficiencies noted include a cracked cast-iron sewer stack, inoperable sump pump with sparking outlet, cracked roof vent stack, and failed tub diverter valve.
- SewerSewer lateral lines are open and flowing; light scaling is present on the cast-iron portion but not enough to require cabling — no issues flagged.
- PestVisual WDI inspection of SFR/Attached Carport at 9835 Portage Drive found no visible evidence of wood destroying insects (termites, carpenter ants, carpenter bees, or reinfesting wood boring beetles); no treatment recommended.
- PlumbingA crack in the main sewer stack's cast-iron section is causing water to leak onto the basement floor; the sump pump is inoperable with a full sump well and a sparking outlet (both need replacement); the water heater expansion tank has a rusted fitting needing replacement; and the tub diverter valve has failed, requiring tub faucet replacement.
- RoofOne metal roof exhaust vent stack is cracked, has been taped, and has lifted flashing — needs replacement; tree limbs are contacting the structure and should be cut back.
- Electrical100-amp Eaton service panel in basement is functional; 2-prong ungrounded outlets are present throughout; a functioning smoke detector should be installed in the basement near gas appliances.
- HVACGoodman central split system (manufactured 2015, 2.5-ton condenser) is functioning correctly but requires annual cleaning and servicing as it is over 10 years old.
- FoundationPoured concrete basement foundation is in satisfactory condition with no moisture detected and no deficiencies observed in basement walls or stairs; perimeter insulation is absent and adding insulation is suggested.

9835 Portage Drive
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of multi-family property found the home in generally good condition with no structural issues; deficiencies noted across HVAC, plumbing, electrical, foundation, and interior systems.
- SewerSewer lateral video scope was performed; no damages or blockages were observed, lines are PVC all the way through and are open and flowing.
- PestVisual WDI inspection of duplex found no visible evidence of wood destroying insects (termites, carpenter ants, carpenter bees, or wood boring beetles); no treatment recommended.
- HVACSecond-floor York (2017) HVAC system was inoperable from the thermostat with all breakers on — needs serviced, cleaned, and loose power switch secured; filter inaccessible due to tight door; basement Trane (2016) forced-air furnace satisfactory; Trane XR 2-ton condenser (2017) and Emerson 2.5-ton condenser (2020) present.
- PlumbingBasement Water Heater #1 (GE, 2011, 40 gal natural gas) requires a TPR blowoff leg installed to code; second-floor Water Heater #2 (Rheem, 1984, 40 gal natural gas) is nearing end of expected lifespan and needs replacement; soft spot present in third-floor bathroom floor between toilet and tub.
- FoundationBasement is slightly damp due to dried and cracked mortar in the stone foundation — replace cracked mortar and apply Drylok-type waterproofer; basement perimeter insulation is hanging loose and needs reset.
- ElectricalTree limbs are pushing on overhead power lines — contact Ameren to trim; smoke detectors are missing throughout the home; GFCI outlet absent at second-floor unit laundry; two Siemens 100-amp panels appear functional.
- RoofArchitectural shingle and roll roofing estimated 5–7 years old in satisfactory condition; masonry chimney, skylights, metal flashings, soffit, fascia, and gutters all satisfactory; no roof ventilation present.
- WindowsInterior windows (double hung, single hung, fixed) are screwed shut and could not be tested for operation; exterior windows in satisfactory condition.

811 Russell Boulevard
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies including a blocked sewer lateral, broken exterior GFCI outlet, inoperable kitchen exhaust fan, broken thermostat, disconnected fireplace flue handle, cracked basement windows, and older termite damage; roof (1-3 years old) and structure were satisfactory with no structural issues noted.
- SewerSewer lateral line is completely blocked with debris and tree roots; two sections of the cast-iron pipe are cracked allowing root intrusion — hydroflushing and sleeve repairs at both cracks are recommended.
- PestVisible evidence of wood destroying insects found: older termite damage present on wood exterior door trim; no live insects observed; treatment with borate-based solution recommended.
- SewerThe sewer lateral line is completely blocked with debris and tree roots; two sections of the cast-iron portion are cracked, allowing root intrusion — lateral requires hydroflushing and sleeve repairs at the two cracks.
- ElectricalExterior GFCI outlet at front corner is broken, won't reset, and is loose from the wall; two outlets in the rear add-on room have reversed hot/neutral wiring and a loose mounting; laundry area lacks GFCI-protected outlet; kitchen exhaust fan is inoperable with no power.
- HVACThermostat battery door is broken and keeps popping open, canceling the HVAC system and requiring repair or replacement; Goodman central split system (2.5-ton A/C, mfgd 2019) and Goodman forced-air gas furnace are otherwise functioning satisfactorily.
- PlumbingState brand 40-gallon natural gas water heater (manufactured 2019) is functioning properly; copper supply pipes are satisfactory; sump pump not present.
- RoofArchitectural shingle roof estimated 1-3 years old is installed correctly and in satisfactory condition; gable-end ventilation, metal vent stacks, gutters, and downspouts are all satisfactory.
- FoundationPoured concrete foundation is in satisfactory condition; common corner cracks observed and inspector recommends sealing with heavy-duty epoxy paste; no moisture detected in basement.
- PestOlder termite damage is visible on the exterior door trim with no other signs of active infestation found; treatment with a borate-based solution (e.g., Bora-Care) is recommended unless seller can prove prior treatment.
- WindowsFront living room window will not lock — lock mechanism is loose and needs securing; two basement glassblock windows have small cracks and need repair or replacement; fireplace flue handle in living room is disconnected and will not open the flue.

7541 Norwalk Lane
St. Louis, Missouri
Normandy, Missouri
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies including inoperative AC unit, full sewer blockage with tree root intrusion, unsecured attic ladder, missing carport storm door, and bathroom window that won't lock; home otherwise appears in good condition with no structural issues.
- SewerNo structural damage observed to sewer lateral lines; however, a full blockage is present at the city main tie-in, excessive tree root intrusion found in the clay section, and scaling/buildup in the cast-iron section; hydroflushing recommended, and a Fireball bottle in the laundry drain needs removal.
- PestVisual inspection of 5563 Winchelsea Drive found no visible evidence of wood destroying insects (termites, carpenter ants, carpenter bees, or reinfesting wood boring beetles); no treatment recommended.
- RoofArchitectural shingle roof estimated 1-3 years old is installed correctly and in satisfactory condition; ventilation, flashings, soffit, fascia, and gutters all satisfactory.
- FoundationSlab-on-grade poured concrete foundation is in satisfactory condition with no structural issues observed; wood frame wall structure satisfactory; attic ladder is not secure and needs to be stabilized; attic insulation (fiberglass batts) is low and should be added for improved efficiency.
- Electrical100-amp overhead service with Cutler Hammer panel in utility room is functional; 2-prong ungrounded outlets are present throughout; smoke detectors tested satisfactory.
- HVACInternational Comfort gas furnace (manufactured 2002) is satisfactory but over 10 years old and should be serviced yearly; Coleman 2-ton AC condenser (manufactured 2021) failed to operate during inspection and requires servicing.
- PlumbingCopper supply pipes satisfactory; Hotpoint electric 40-gallon water heater (manufactured 2007) is functional but aged; a Fireball bottle was thrown down the laundry drain and needs to be removed; waste pipe materials are PVC, cast iron, and clay.
- SewerFull blockage present at the city main tie-in with excessive tree root intrusion in the clay section and scaling/buildup in the cast-iron section of the sewer lateral line; hydroflushing recommended for proper flow and to prevent backups.
- WindowsBathroom window is older and won't lock and needs to be adjusted; caulking of window interiors is recommended as needed.

5563 Winchelsea Drive
Normandy, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection at 4065 Schiller Pl identified multiple deficiencies including a safety-hazard electrical system, full HVAC replacement needed, corroded plumbing supply lines, basement wall cracks, and window defects; no structural issues found.
- PestVisual inspection of SFR at 4065 Schiller Place found no visible evidence of wood destroying insects (termites, carpenter ants, carpenter bees, or wood boring beetles); no treatment recommended.
- ElectricalFederal Pacific fuse box (last inspected 1977) requires update; knob-and-tube wiring still present throughout but could not be tested due to no power; 100-amp service; smoke detectors missing throughout home including near basement gas appliances.
- HVACRPJ gas furnace estimated 40 years old is heavily rusted and requires replacement; AC condenser has been removed and is not present; full HVAC system replacement recommended.
- FoundationLarge cracks in basement walls require sealing with epoxy injections to prevent moisture intrusion; exterior basement finished wall cracks also noted; no moisture detected at time of inspection.
- PlumbingSmall section of water supply lines is galvanized steel and heavily corroded/rusted, requiring replacement; Reliance 40-gallon natural gas water heater (manufactured 2014) is functional but missing the TPR valve discharge pipe, which must be replaced.
- RoofArchitectural shingle roof estimated 2-5 years old and in satisfactory condition; loose gutter downspout and fascia panel at rear patio need securing; missing soffit panels need replacement.
- WindowsRear-facing second-floor window is out of frame and needs to be reset; three missing window panes at rear of home require replacement; rear patio door is missing and must be replaced.

4065 Schiller Place
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of a 4-unit brick building found good overall condition with no structural issues; deficiencies include an active plumbing leak in Unit #1N, reverse-slope drain plumbing in three kitchens, loose tub faucets in Units #2N and #2S, a damaged North basement door, a cracked South basement wall, and window deficiencies in Unit #1S.
- SewerSewer lateral scope performed in each of 2 basement sewer stacks; all lines are open and flowing with no damages or obstructions observed; most of the line is PVC.
- PestWood Destroying Insect inspection of 4-family complex at 3541 Oregon Avenue found no visible evidence of wood destroying insects; no action or treatment recommended.
- RoofTPO roofing inspected via drone is rated satisfactory and estimated 1–3 years old; metal gutters present; no deficiencies noted.
- ElectricalEach of the four units has a Square D 100-amp service panel located in the basement with breaker-type overcurrent devices; outlets tested satisfactory in all units; one inoperable smoke detector noted in the North basement (Unit #2N).
- HVACThree units (1N, 1S, 2S) have Ameristar gas furnaces manufactured in 2006; Unit #2N has a Guardian gas furnace manufactured in 2019; all four units have 2021 Guardian 2-ton split-system AC condensers; all mechanicals appear to be working properly.
- PlumbingActive plumbing leak discovered behind Unit #1N washer/dryer combo causing water to spill to basement floor; under-sink drain plumbing has a reverse slope in Units #1S, #2N, and #2S kitchens; loose tub faucets in Units #2N and #2S; toilet water supply shut off in Unit #2S; all four 2006-manufactured water heaters (two 40-gal Hotpoint, two 30-gal GE) appear functional.
- FoundationStone basement foundation with unfinished floors; basement stairs and walls rated satisfactory; one long vertical crack in the South basement wall needs to be sealed to prevent potential water intrusion; North basement door is damaged and has come loose from its frame and needs replacement.
- WindowsA front-facing window in Unit #1S needs the locking mechanism replaced; several windows in Unit #1S are hard to open and need window balances adjusted.

3541 Oregon Avenue
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of 30 Graeler Drive found the property in generally good condition with no structural issues; deficiencies noted across site, roofing, electrical, plumbing, pest, and windows systems.
- Radonaverage result was 5.1 pCi/L, with a minimum of 0.6 pCi/L and a maximum of 12.1 pCi/L over the 47-hour test period
- SewerSewer lateral inspection found tree roots intruding into one small section of cast-iron pipe indicating a crack, with heavy scaling also present; inspector recommends hydroflushing and re-cameraing the lines, with cabling/clearing and root foam as a potential remediation option.
- PestVisible evidence of wood destroying insects found: older termite damage on wood trim around door and on wood fence; borate-based solution treatment recommended; no live insects observed.
- PestOlder termite damage present on wood trim around the garage door and on the wood fence; replacement of damaged wood and borate-based treatment (Bora-Care) recommended.
- Electricalexposed wood from previously removed meter needs covering. rear patio GFCI outlet won't reset and remains hot after tripping. second exterior outlet needs GFCI replacement. laundry room lacks GFCI outlet. 2-prong ungrounded outlets present throughout interior
- RoofSquirrels have chewed the flashing on one roof vent pipe almost completely; vent pipe flashing requires replacement; architectural shingles estimated 7–10 years old and otherwise satisfactory.
- HVACLennox 2.5-ton AC condenser (manufactured 2007) operates properly but needs annual cleaning and servicing due to age; Goodman electric furnace (manufactured 2026) is performing properly.
- PlumbingTree roots have intruded into one section of cast-iron waste pipe indicating a crack, with heavy scaling present; hydroflush and re-camera recommended; Bradford White 50-gallon gas water heater (manufactured 2002) is functional but nearing end of expected lifespan.
- WindowsFour windows and the rear patio door have broken seals and need repair or replacement; one broken rear-facing window pane also requires replacement.

30 Graeler Drive
St. Louis, Missouri
WHAT THE RECORDS SHOW
78 eligible recordsGreensmith Home Inspection LLC has 79 attributed profile entries; 78 eligible public records meet the current evidence rules across 77 properties, with source dates from January 2022–August 2026.
The business profile states 12 years in business. Fresh House profile registration is a separate date and is not treated as a founding date.
The business profile lists Home Inspection, New Construction, Pest, and Sewer Scope. Separately, eligible Fresh House records contain Home Inspection, HVAC, and Pest as status-neutral topics.
Reviewed record examples in this cohort include radon measurement, new-construction inspection, sewer-scope findings, and WDI findings. Each example remains tied to its source record and is not used to infer a credential or frequency. One reviewed inspection record also documents status-neutral whole-home findings involving electrical, roof, foundation, HVAC, plumbing, windows, and moisture or mildew conditions; it does not establish that repairs were completed.
4 records use the Fresh House upload date because a source-document date is not available; the fallback is labelled rather than presented as a work date.
Record topics and locations do not establish current business coverage, credentials, licensing, or that proposed work was completed.
Original home-inspection reports are not republished on this profile; the public page presents extracted findings.
Documented work locations
Every city/state below comes from the current eligible Fresh House record cohort. Record geography is not a claim about the business's service area.
- St. Louis, Missouri(32)
- St. Louis, MO(9)
- Florissant, Missouri(8)
- Jennings, Missouri(3)
- Berkeley, MO(2)
- Florissant, MO(2)
- O'Fallon, Missouri(2)
- St. Peters, Missouri(2)
- Wentzville, Missouri(2)
- Ballwin, Missouri(1)
- Ballwin, MO(1)
- Chesterfield, Missouri(1)
- De Soto, Missouri(1)
- Ferguson, Missouri(1)
- Ferguson, MO(1)
- Hazelwood, Missouri(1)
- Hazelwood, MO(1)
- Imperial, Missouri(1)
- Jennings, MO(1)
- Lake St. Louis, Missouri(1)
- Maryland Heights, Missouri(1)
- Normandy, Missouri(1)
- St. Charles, Missouri(1)
- Troy, Missouri(1)
- Wright City, Missouri(1)
Quick answers about this profile
Answers grounded in the visible Fresh House evidence cohort
What does the documented radon record for Greensmith Home Inspection LLC show?
A source record dated July 3, 2026 documents a 71-hour test using a RadStar RS300: 2.8 pCi/L average, 0.8 pCi/L minimum, and 5.0 pCi/L maximum. This is a record example, not a certification claim.
Is new-construction inspection evidence documented for Greensmith Home Inspection LLC?
Yes. The current eligible cohort includes 2 reviewed new-construction inspection records: July 14, 2026 at a O'Fallon, MO property and July 2, 2026 at a Chesterfield, MO property. Their categorized findings have unknown work status, so they document inspection observations rather than completed repairs. They do not establish credentials, frequency, coverage, or every service currently offered.
What does a documented sewer-scope record for Greensmith Home Inspection LLC show?
A source record dated July 28, 2026 describes a collapsed line near a cast-iron stack. It is one bounded finding example; Fresh House does not infer a frequency from it.
What does a documented WDI record for Greensmith Home Inspection LLC show?
A source record dated July 24, 2026 notes older termite damage on front landscape timbers and no live insects observed. Its categorized findings have unknown work status; it does not document completed treatment or repair and does not establish a WDI licence or certification.
What coverage is stated, and where is work documented for Greensmith Home Inspection LLC?
The Fresh House business profile states coverage as: St. Louis City, St. Louis County, Saint Charles County, Warren County, Jefferson County. Eligible Fresh House records are associated with properties in St. Louis, Missouri, St. Louis, MO, Florissant, Missouri, Jennings, Missouri, Berkeley, MO, Florissant, MO, O'Fallon, Missouri, St. Peters, Missouri, Wentzville, Missouri, Ballwin, Missouri, Ballwin, MO, Chesterfield, Missouri, De Soto, Missouri, Ferguson, Missouri, Ferguson, MO, Hazelwood, Missouri, Hazelwood, MO, Imperial, Missouri, Jennings, MO, Lake St. Louis, Missouri, Maryland Heights, Missouri, Normandy, Missouri, St. Charles, Missouri, Troy, Missouri, and Wright City, Missouri. These are documented record locations, not a claim about the business's service area. Record locations do not expand the profile-stated service area.
Are the original home-inspection reports for Greensmith Home Inspection LLC public?
No. Fresh House does not republish the original home-inspection reports on this professional profile. The public page presents extracted findings while the source reports remain withheld.
Contact Greensmith Home Inspection LLC
By the Numbers
Profile location and stated coverage
Business profile states coverage as: St. Louis City, St. Louis County, Saint Charles County, Warren County, Jefferson County
SERVICES AND RECORD TOPICS
16 unique itemsServices listed on the business profile
Greensmith Home Inspection LLC's Fresh House profile lists these services. This is a business-profile statement, not a claim that each service appears in the public record history.
Business-stated services: Home Inspection, New Construction, Pest, and Sewer Scope. This list comes from Greensmith Home Inspection LLC's current Fresh House profile and is not inferred from property records.
New Construction is listed on Greensmith Home Inspection LLC's current Fresh House business profile. It is not inferred from property records and is not presented here as completed work.
Pest is listed on Greensmith Home Inspection LLC's current Fresh House business profile. It is not inferred from property records and is not presented here as completed work.
Sewer Scope is listed on Greensmith Home Inspection LLC's current Fresh House business profile. It is not inferred from property records and is not presented here as completed work.
Inspection topics in Fresh House records
These status-neutral topics come from the eligible Fresh House record cohort. A topic does not by itself establish completed work, a current business offering, a credential, or service coverage.
Record-evidenced topics: Home Inspection, HVAC, and Pest. They describe what appears in eligible records; they do not establish completion, frequency, current offerings, credentials, or coverage.
Home Inspection appears in 75 eligible Fresh House records as a status-neutral topic. That evidence does not by itself establish completion, a current offering, credentials, or service coverage.
HVAC appears in 1 eligible Fresh House record as a status-neutral topic. That evidence does not by itself establish completion, a current offering, credentials, or service coverage.
Pest appears in 3 eligible Fresh House records as a status-neutral topic. That evidence does not by itself establish completion, a current offering, credentials, or service coverage.
Reviewed source-record examples
Each item is tied to one or more reviewed upload IDs in the current eligible cohort. These are bounded source examples, not an unqualified service, frequency, credential, coverage, or typical-price claim.
Fingerprint-matched source examples: Home inspection findings, Sewer scope, WDI and pest inspection, Radon measurement, New-construction inspection, Electrical inspection findings, Roof inspection findings, Foundation inspection findings, and 4 more. Each example remains record-specific and is not generalized into frequency, coverage, credentials, a current offering, or a typical price.
Home inspection findings in one reviewed record dated July 28, 2026 cover electrical, roof, foundation, HVAC, plumbing, windows, and moisture or mildew conditions. The status-neutral findings do not establish that repair work was completed.
Sewer scope evidence in one reviewed record dated July 28, 2026 describes a collapsed line near a cast-iron stack. It is one bounded finding example, not a frequency or coverage claim.
WDI and pest inspection evidence in one reviewed record dated July 24, 2026 notes older termite damage on front landscape timbers and no live insects observed. Its findings have unknown work status, do not document completed treatment, and do not establish a licence or certification.
Radon measurement evidence in one reviewed record dated July 3, 2026 documents a 71-hour test using a RadStar RS300: 2.8 pCi/L average, 0.8 pCi/L minimum, and 5.0 pCi/L maximum. It is a record example, not a certification claim.
New-construction inspection evidence appears in 2 reviewed records: July 14, 2026 at a O'Fallon, MO property and July 2, 2026 at a Chesterfield, MO property. The O'Fallon source describes a new single-family home and 13 observed deficiencies. Their categorized findings have unknown work status, so they document inspection observations rather than completed repairs and do not establish frequency or coverage.
Electrical inspection findings are tied to 2 reviewed records. One dated July 6, 2026 identifies a recalled Sylvania panel; another status-neutral whole-home record includes electrical findings. They do not establish completed repair work or an electrical credential.
Roof inspection findings are tied to 2 reviewed records. One dated July 1, 2026 supports a drone-assisted roof-inspection example; use of drone imagery does not establish an FAA credential, completion, or frequency.
Foundation inspection findings appear in one reviewed whole-home record dated July 28, 2026 as status-neutral foundation observations. The record does not establish completed repair work, frequency, a credential, or a separate current service offering.
HVAC inspection findings appear in one reviewed whole-home record dated July 28, 2026 as status-neutral HVAC observations. The record does not establish completed repair work, frequency, a credential, or a separate current service offering.
Plumbing inspection findings appear in one reviewed whole-home record dated July 28, 2026 as status-neutral plumbing observations. The record does not establish completed repair work, frequency, a credential, or a separate current service offering.
Windows inspection findings appear in one reviewed whole-home record dated July 28, 2026 as status-neutral windows observations. The record does not establish completed repair work, frequency, a credential, or a separate current service offering.
Moisture and mildew findings appear in one reviewed whole-home record dated July 28, 2026 as status-neutral moisture or mildew observations. The record does not establish completed repair work, frequency, a credential, or a separate current service offering.
Inspections, repairs, photos, document what you know about a property.