- Home InspectionWhole-home inspection of single-family property identified active roof leaks, HVAC ductwork issues, electrical deficiencies, and interior ceiling damage requiring repair before occupancy.
- RoofExtensive damage to 3-tab shingled roof (estimated 15 years old) with tarpaper exposed, tattered roof tarp in place, active roof leaks present, and gutters clogged with leaves and debris.
- HVACHVAC flexible ductwork is twisted and does not heat or cool evenly per occupant; furnace filter is missing; AC compressor (International Comfort, Mfgd 2018) is functional but dirty and needs cleaning.
- ElectricalTree limbs are pushing on overhead power lines; one living room outlet has no power and needs repair or replacement; ungrounded two-prong outlets are present throughout the home.
- PlumbingPVC supply pipes are satisfactory; Rheem 40-gallon electric water heater (Mfgd 2018) is functional with T&P relief valve present, but lacks a fuel disconnect.
- FoundationSlab-on-grade foundation with concrete block material and wood frame wall structure observed in satisfactory condition with no structural deficiencies noted.
- WindowsExterior windows (wood, vinyl, aluminum) and interior windows (double hung, fixed) are in satisfactory condition with no defects observed.
Fresh House generated structured findings from a documented professional record.
6809 Saint Olaf Drive
Berkeley, MO
Berkeley, MO
- Home InspectionWhole-home inspection of redacted identified multiple defects across plumbing, HVAC, electrical, windows, roofing, and foundation systems; no structural deficiencies were observed.
- PlumbingCopper supply plumbing lines have been cut and removed from the home and need to be replaced; water heater T&P relief valve discharge pipe also needs replacement.
- HVACAC condenser lines (2.5-ton Goodman, mfgd 2020) have been cut from the system and need replacement; Whirlpool gas furnace (mfgd 2016) needs cleaning and servicing, and vegetation must be cleared from the condenser.
- ElectricalSmoke detectors are missing/non-operational throughout the home; bathroom GFCI outlet is older and will not reset and needs replacement; kitchen GFCI outlet has a broken ground prong that needs removal; most interior outlets are two-prong ungrounded.
- WindowsOne broken window needs replacement and caulking is needed around windows throughout the exterior.
- RoofTree limbs are contacting the roof structure and need to be cut back; a large roof vent over the rear porch is leaning and needs to be straightened; 3-tab shingle roof covering is estimated 15 years old and in satisfactory condition.
- FoundationConcrete floor in the rear utility room is severely bowed, though it does not appear to affect the structure; poured concrete foundation is otherwise satisfactory.
Fresh House generated structured findings from a documented professional record.
6317 Jackson Avenue
Berkeley, MO
5631 Sapphire Avenue
Jennings, MO
505 Ridge Drive
Florissant, MO
- Home InspectionWhole-home inspection of 334 Caithness Rd identified 16 items needing attention including electrical deficiencies, a basement wall crack, aging HVAC, and deferred maintenance items; no structural deficiencies were observed.
- PestOlder termite damage is present on wood landscape timbers; no damage or active presence was observed to the structure, but treatment is recommended every 3 to 5 years for termites/wood destroying insects.
- RoofThree-tab shingled roof is estimated 10 years old and appears to be performing with patching done; missing downspout on front corner, wood fascia needs scraping and painting with openings sealed, and tree limbs should be cut back from hanging over the roof.
- FoundationOne horizontal crack approximately 8 feet long on the west basement wall needs to be repaired with epoxy injection; no moisture intrusion was observed.
- ElectricalAll electric outlets in the living room are inoperable and need repair/replacement, the kitchen GFI outlet is burned out and needs replacement, smoke detectors are missing throughout the home, and tree limbs are pushing on overhead power lines requiring Ameren to address.
- HVACGoodman central split system furnace and air conditioner (both manufactured 2005) appear to be performing but need to be cleaned and serviced by a licensed HVAC technician.
- PlumbingTub faucet handle is disconnected and needs to be reattached; water heater (State, electric, 40 gal, manufactured 2019) is satisfactory with supply pipes (copper) and waste pipes (cast iron) in satisfactory condition.
Fresh House generated structured findings from a documented professional record.
334 Caithness Road
St. Louis, Missouri
- Home InspectionWhole-home inspection of 333 Lancashire Rd, St Louis, MO 63137 identified six actionable items including roof deficiencies, non-functioning smoke detectors, slow drains, missing kitchen exhaust fan, and a missing exterior siding panel; no structural deficiencies were observed.
- RoofShingled roof is estimated 25 years old with two damaged shingles, previous patching, and a large tarp present; per seller's agent the roof is in process of being replaced; tree limbs are hanging over and contacting the roof structure.
- ElectricalBedroom smoke detectors are present but not functioning; inspector recommends installing functioning smoke detectors throughout the house; 100-amp General Electric panel with breakers is satisfactory.
- HVACGoodman gas forced-air furnace (manufactured 2005) and American Standard 2-ton split-system AC condenser (manufactured 2004) are both over 10 years old and should be checked, cleaned, and serviced yearly; kitchen exhaust fan is not present as the previous wall fan was removed and paneled over.
- PlumbingBathroom sink and bathtub were very slow to drain and drain lines likely need to be cleared; water heater is a State 40-gallon natural gas unit manufactured in 2022 and is satisfactory; copper supply pipes and PVC waste pipes are satisfactory.
- FoundationPoured concrete foundation with basement access inspected; no moisture detected, no structural deficiencies observed, and basement walls are satisfactory; perimeter insulation is not visible and adding insulation is suggested.
- WindowsVinyl and steel-framed basement windows inspected and found to be in satisfactory condition with no deficiencies noted.
Fresh House generated structured findings from a documented professional record.
333 Lancashire Road
St. Louis, Missouri
Jennings, Missouri
- Home InspectionWhole-home inspection of a single-family property identified multiple deficiencies across roofing, structure, HVAC, plumbing, electrical, pest, and exterior systems requiring repair, replacement, or further evaluation before closing.
- ElectricalMissing and non-functional smoke detectors need replacement with operational units; busted porch light at rear patio has exposed hot wires; ungrounded two-prong outlets are present throughout the home; exterior electric noted as needing repairs.
- HVACThe Ruud furnace (manufactured 2016, 75,000 BTU) has had its heat exchanger removed and needs it replaced, rendering the HVAC inoperable; the HVAC exhaust duct has been torn loose; thermostat batteries need replacement; Ruud 2-ton condenser (2016) is present.
- PlumbingInterior plumbing includes galvanized steel supply lines that need replacement; the water heater exhaust has lost its seal due to the furnace exhaust being ripped away; the 40-gallon Rheem water heater (manufactured 2018) shows signs of rust from previous moisture intrusion.
- RoofThree-tab shingled roof estimated 20 years old is extensively patched with damaged/lifted shingles and needs full replacement; damaged soffit on front corner, tree limbs overhanging roof, and debris-filled/bent gutters also require attention.
- FoundationOne long horizontal crack is present on the north basement wall requiring repair; multiple cracks in the exterior foundation need epoxy injection sealing; signs of previous moisture intrusion with musty smell observed in basement; section of driveway concrete has sunk creating a trip hazard.
- PestOlder termite damage is present on wood window shims, overhead garage door trim, and wood landscape timbers; full termite treatment for the home is recommended.
- WindowsOne boarded-up window pane needs replacement and four missing or damaged window screens need to be replaced.
Fresh House generated structured findings from a documented professional record.
2463 Shannonaire Drive
Jennings, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of a single-family property identified multiple deficiencies across roofing, structure, HVAC, plumbing, electrical, pest, mold, windows, and foundation systems, with no structural deficiencies observed but numerous repair and further-evaluation items noted.
- PlumbingRear exterior faucet is not connected to plumbing and needs properly plumbed; water heater unit has been removed and needs replaced; signs of possible plumbing leaks are present under the second-floor bathroom vanity sink.
- ElectricalSmoke detectors throughout the home are not operational and need replacement; a missing light fixture with exposed hot wires and a missing outlet cover were observed in the interior; wasp nests are present in the rear exterior electric outlet.
- RoofMissing roof sheeting over front porch with rotted wood framing, collapsed roof section over walkout basement, lifted shingles needing sealing, soft roof decking, gaps in fascia board, loose aluminum soffit siding, and loose/unleveled gutters with missing splashblocks and debris.
- PestOlder termite damage is present on wood framing of the walkout basement and on exterior siding; full termite treatment on the property is recommended unless seller proves prior treatment.
- WindowsDamage observed to window on west side of home requiring repair and caulking, and one broken window pane needs replacement.
- FoundationBasement foundation walls of cinder block construction have cracks and missing mortar allowing moisture intrusion; replacement of missing mortar and sealing of cracks is recommended.
- HVACSplit system refrigerant lines have been cut and the HVAC furnace coil has been removed from the basement; the digital thermostat is inoperable and would not power up after battery replacement.
- MoldMold on the main-floor living room ceiling indicates a likely plumbing leak in the second-floor bathroom east of the bathtub; plumbing leak repair and mold/mildew removal are recommended.
Fresh House generated structured findings from a documented professional record.
2363 Gardner Drive
St. Louis, Missouri
- Home InspectionWhole-home inspection of 225 Sadonia Avenue, St. redacted identified multiple deficiencies including cut plumbing supply lines, aged HVAC system needing replacement, damaged electrical meter box, basement moisture with mildew, sewer blockage, broken window pane, missing soffit panels, and bedroom ceiling damage.
- PlumbingCopper plumbing supply lines have been cut and need full replacement; gas water heater (Hotpoint, 40 gal, manufactured 2011) is present with satisfactory T&P relief valve.
- SewerSewer lateral videoscope was performed to the home; no pipe damages were observed, however a blockage is present that needs cleared and buildup needs cabled/removed.
- HVACHVAC furnace is estimated 40–50 years old (Space Conditioner, evap lines cut) and the Comfortmaker AC compressor was manufactured in 1992; the entire HVAC system needs replacement.
- ElectricalDamaged electrical meter box needs replacement; a loose live wire hanging from the basement ceiling needs to be capped immediately; 2-prong ungrounded outlets are present throughout the home.
- RoofArchitectural shingle roof is estimated 5 years old and performing; tree limbs should be cut back from the roof, missing soffit panels need replacement, and loose soffit panels need to be secured.
- MoldA steady drip from cut copper supply lines has pooled onto the basement floor, resulting in mildew growth on wood paneling and mold-like growth observed on basement walls.
- FoundationBasement moisture condition is damp due to cut plumbing supply lines dripping at the water meter; basement walls show damage from moisture and require repair.
- WindowsOne broken window pane on the corner bedroom needs replacement.
Fresh House generated structured findings from a documented professional record.
225 Sadonia Avenue
St. Louis, MO
- Home InspectionWhole-home inspection of single-family property at 2221 Kipp Ct identified multiple repair items including missing copper plumbing lines, spot mold in basement, a non-functional GFCI outlet, loose exterior electrical outlet, missing thermostat faceplate, tree limbs contacting the roof, and a detached rear gutter, with no structural deficiencies observed.
- PlumbingCopper supply plumbing lines have been cut and a good amount of plumbing line is missing and will need replaced; the copper discharge pipe on the water heater has been removed and needs replaced; the water meter handle is seized shut and needs lubricated; master bathroom tub requires caulking and a missing handle replacement.
- MoldA water line has been cut and water has pooled on the basement floor, resulting in spot mold; after replacing the missing pipe, pooled water and mold must be cleaned up and removed.
- HVACGoodman central split system (manufactured 2013) with forced air heating and 2.5-ton condenser appears functional, but the thermostat faceplate has been removed and needs replaced; system is over 10 years old and should be serviced yearly.
- ElectricalExterior outlet at rear patio is loose from the wall and needs secured; GFI outlet in master bathroom will not reset and needs replaced; 100-amp Square D service panel with breakers appears functional.
- RoofArchitectural shingle roof (estimated 5 years old) is satisfactory overall, but tree limbs are hanging over and contacting the roof, the gutter over the rear patio is pulling away from the home and needs realigned, and loose soffit needs to be secured.
- FoundationPoured concrete basement foundation is satisfactory with no structural deficiencies; prior repairs to the basement wall appear effective; basement moisture condition is wet due to a cut water line causing pooled water on the floor.
- WindowsVinyl and aluminum exterior windows are in satisfactory condition; trim around the front living room window needs to be reinstalled.
- PestNo termite or pest presence/damage was observed at the property.
Fresh House generated structured findings from a documented professional record.
2221 Kipp Court
St. Louis, MO
Florissant, Missouri
- Home InspectionWhole-home inspection of 1890 Pyrenees Dr, Florissant, MO found the home in generally good shape with no structural deficiencies; key concerns include a heavy plumbing leak below the kitchen, cracking basement wall repairs, and a 20-year-old HVAC system needing service.
- ElectricalMurray 100-amp service panel located in the basement is a newer panel approved by the City of Florissant (electrical inspection dated 5-3-19); overcurrent protection via breakers is satisfactory and no outlet defects were noted.
- PestNo termite or pest presence or damage was observed at the time of inspection.
- PlumbingA massive leak is present directly below the kitchen from a loose fitting in the supply lines; the main water shut off valve is also leaking at the handle and needs repair; the 40-gallon State natural gas water heater (manufactured 2020) appears functional.
- HVACBryant forced-air gas furnace (71,000 BTU, manufactured 2001) and Bryant 2.5-ton split-system condenser (manufactured 2001) are approximately 20 years old, need cleaning and servicing, but appear to be performing.
- RoofThree-tab shingled roof estimated 10–15 years old is in satisfactory condition; 1–2 shingles are lifted and need to be sealed down, and tree limbs overhanging the roof should be cut back as a large limb has dropped onto the power lines.
- FoundationPrevious repairs to the basement wall are beginning to crack; inspector recommends tearing out old fill and sealing the crack with epoxy injection; no active moisture intrusion was observed but signs of previous moisture were present.
- WindowsExterior windows consist of wood, vinyl, and steel-framed basement windows, all observed in satisfactory condition.
Fresh House generated structured findings from a documented professional record.
1890 Pyrenees Drive
Florissant, Missouri
Florissant, Missouri
- Home InspectionWhole-home inspection of single-family property at 12721 Coachlight Square Dr, Florissant, MO 63033 identified mold in basement, active plumbing leak, HVAC rust damage, missing smoke detectors, and roof/exterior deficiencies; no structural deficiencies observed.
- FoundationPoured concrete basement foundation is satisfactory with no structural deficiencies observed; previous home-made repairs are present on basement walls and appear to be effective.
- MoldMost basement sheetrock has a fine coat of mildew turning into mold caused by a plumbing leak in the master bathroom; after the plumbing leak is repaired, moldy sheetrock needs to be removed and replaced.
- PlumbingDrain line for master bathroom toilet is leaking onto the basement floor; hallway bathroom vanity sink is missing a drain nozzle; pressure regulator needs installation or adjustment due to very low water pressure throughout; Rheem tankless water heater (manufactured 2014) has no temperature and pressure relief valve present.
- HVAC2010 York gas furnace in basement has excessive rust due to proximity to a leaking bathroom drain pipe, loose chipboard needs securing, and furnace needs cleaning and servicing by an HVAC technician; 2011 York 2.5-ton AC compressor appears functional.
- ElectricalLoose electrical outlet at front porch needs to be secured; smoke detectors are not present throughout the home and functional units need to be installed.
- RoofThree-tab shingled roof is performing with shingles estimated at 15 years old; one damaged shingle on the front corner needs replacement, tree limbs need to be cut back from the roof, and minor fascia board damage on the south side needs repair.
- PestNo termite or pest presence or damage was observed at the property.
Fresh House generated structured findings from a documented professional record.
12721 Coachlight Square Drive
Florissant, Missouri
- Home InspectionWhole-home inspection of single-family property at 12030 Lavida Ave, St Louis, MO 63138 identified numerous deficiencies across electrical, HVAC, roofing, plumbing, and other systems, with no structural deficiency observed but a good amount of repairs needed.
- ElectricalFederal Pacific electric panel with recalled Stablok breakers requires replacement due to safety risks; smoke detectors are missing and need replacement; exterior carport outlet needs a new weatherproof cover; tree limbs are pushing on overhead power lines.
- HVACAC compressor (Goodman 2017, 2.5-ton) is severely unlevel and surrounded by vegetation; furnace (Goodman 2013, 80,000 BTU) is dirty and needs cleaning and service by an HVAC technician; thermostat batteries are dead and need replacement.
- Roof3-tab shingle roof estimated 10-15 years old has missing and damaged shingles needing repair; tree limbs are contacting/hanging over the roof; gutters are clogged with leaves and debris; fascia and edge shingles at rear of home are damaged.
- PlumbingSigns of a plumbing leak under the kitchen sink with mildew present; missing showerhead in hallway bathroom; missing toilet seats in master and basement bathrooms; water service was off during inspection preventing full plumbing testing; water heater is a GE 40-gallon natural gas unit manufactured in 2010.
- FoundationPoured concrete basement foundation is satisfactory with no structural deficiency; small exterior cracks noted and should be sealed with urethane caulk; basement has a musty smell with signs of previous moisture intrusion, attributed in part to a leaky kitchen sink draining onto the basement bathroom ceiling.
- WindowsOne broken basement window pane was observed and needs to be replaced.
- PestOlder termite damage is present on the wood fence with no active presence observed on the structure; termite/wood-destroying insect treatment is recommended every 3-5 years.
Fresh House generated structured findings from a documented professional record.
12030 Lavida Avenue
- Home InspectionWhole-home inspection of single-family property identified a major plumbing leak, rotted rear deck decking, damaged rear patio door, older termite damage to fence, 3 missing/inoperable smoke detectors, sunk front walkway, and various maintenance items; no structural deficiencies observed.
- PestOlder termite damage is present to the wood fence; no damage was observed to the structure; spraying for termites/wood-destroying insects every 3–5 years is recommended.
- WindowsExterior windows are vinyl, steel-framed basement windows, and glass block, all in satisfactory condition.
- PlumbingMassive water leak present at the regulator valve under the kitchen sink — water ran full strength across the kitchen floor, requiring water service to be shut off; plumbing could not be fully tested; water heater is a Rheem 40-gallon natural gas unit manufactured in 2014, appears functional.
- HVACGoodman central split system (forced air gas heat, 3-ton electric cooling condenser) manufactured in 2016 appears functional; digital thermostat in hallway; metal ducting and disposable filter in satisfactory condition.
- Roof3-tab shingle gable roof estimated 15 years old is in satisfactory condition; tree limbs are hanging over the roof and need to be cut back; gutters contain leaves and debris that need to be removed.
- ElectricalNewer Eaton 100-amp service panel with breakers is satisfactory; 3 inoperable/missing smoke detectors need replacement; electric outlets could not be tested due to no power during inspection.
- FoundationPoured concrete basement foundation is in satisfactory condition with no moisture detected; a previous exterior foundation repair appears to be effective.
Fresh House generated structured findings from a documented professional record.
11830 Seven Hills Drive
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property at 11632 Criterion Ave., St. Louis, MO 63138 identified multiple defects across plumbing, electrical, roofing, and other systems; no structural deficiencies were observed.
- PlumbingExterior faucet is seized shut and needs replacement; hallway bathroom tub faucet turns on but will not turn off and has worn the tub finish, requiring faucet replacement and tub finish repair; hallway toilet will not flush as the handle is not connected to the flange valve.
- SewerSewer lateral videoscope was performed and revealed no structural damage or obstructions, but tree roots are intruding into the lines and buildup/scaling is present; technician recommends cabling/clearing the lines.
- ElectricalTree limbs are pushing on overhead power lines and Ameren should be contacted to trim them; kitchen GFI outlet will not reset and needs replacement; one inoperable smoke detector in the basement needs replacement.
- HVACGoodman gas forced-air furnace (2013, 80,000 BTU) and DuCane central split-system condenser (2013, 2.5-ton) are both functioning with no deficiencies observed; disposable filter replacement is suggested.
- Roof3-tab shingle roof estimated at 10 years old is performing satisfactorily; missing soffit panels need replacement, front guttering is loose and needs securing, and a missing downspout piece at the front corner needs replacement.
- FoundationPoured concrete foundation is in satisfactory condition; an exterior foundation crack has been repaired with urethane caulk and no moisture intrusion was observed.
- WindowsWindows (vinyl, aluminum, and steel-framed basement windows) are in satisfactory condition overall, but caulking/sealing around windows is needed where gaps are present.
- PestNo termite damage or pest presence was observed at the property; termite treatment appears to have been previously performed.
Fresh House generated structured findings from a documented professional record.
11632 Criterion Avenue
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property identified multiple defects across roofing, foundation, plumbing, electrical, HVAC, windows, and interior systems requiring repair or further evaluation.
- FoundationConcrete foundation appears in good shape overall, but small exterior cracks are present that need repaired with epoxy injection; basement moisture condition is wet due to a leaking laundry faucet bib.
- RoofThree tab shingles estimated 7-10 years old are generally satisfactory, but three shingles are damaged and need replaced, tree limbs need cut back from the roof, and gutters need leaves and debris removed.
- ElectricalSmoke detectors are inoperable or not present throughout the home and need to be installed; GFI outlet to the left of the kitchen sink will not reset and needs replaced.
- HVACGoodman central split system furnace and AC compressor (both manufactured 2014) need cleaned and serviced by an HVAC technician; hallway bathroom ventilator is inoperable and needs repaired or replaced.
- PlumbingLaundry faucet bib is leaking onto the basement floor with pooled water, hallway bathroom tub would not shut off, master bathroom toilet will not flush, and the water heater TPR valve needs a discharge pipe installed.
- WindowsDamaged wood around the front window needs to be replaced.
- UnclassifiedFront porch has a very large crack that needs sealed; missing exterior trim panel at front corner exposes wood framing; garage door opener pulled off track needs reset; kitchen cabinets need secured to the wall; dishwasher is inoperable and needs repaired or replaced; ceiling damage over rear patio door needs repair.
Fresh House generated structured findings from a documented professional record.
11620 Petite Chalet Drive
St. Louis, Missouri
- Home InspectionWhole-home inspection of 10651 Dunkeld Cir, St Louis, MO 63137 identified multiple deficiencies including a dirty 1992 Lennox furnace needing service, inoperable oven and dishwasher, termite damage on exterior wood door, missing front porch handrails, damaged front storm door, and a crack in the dining room ceiling; no structural deficiencies were observed.
- WindowsExterior windows (wood, aluminum, and steel-framed basement windows) are in satisfactory condition with no deficiencies noted.
- UnclassifiedFrigidaire range oven is inoperable and needs repair per occupant; GE dishwasher is inoperable per occupant; damaged front storm door needs repair; missing handrails on front porch need replacement; loose exterior faucet at front porch needs to be secured; crack in dining room ceiling needs to be sealed.
- HVACLennox furnace manufactured in 1992 is dirty and needs to be cleaned and serviced by an HVAC technician; Kelvinator 2-ton split system condenser (manufactured 2004) appears functional but is over 10 years old and should be serviced yearly.
- Roof3-tab shingle roof estimated 10 years old is in satisfactory condition; one asphalt shingle has lifted and needs to be sealed back down, and gutters need leaves and debris removed.
- Electrical100-amp overhead electrical service with Crouse-Hinds panel located in basement; breakers and smoke detectors tested satisfactory with no deficiencies noted.
- PlumbingCopper supply pipes and PVC waste pipes are in satisfactory condition; Rheem 40-gallon natural gas water heater manufactured in 2022 appears functional with T&P relief valve present.
- FoundationPoured concrete basement foundation is in satisfactory condition with no structural deficiencies, no moisture detected, and no deficiencies observed on basement walls; perimeter insulation is absent and adding insulation is suggested.
- PestOlder termite damage is present on the exterior of a wood door; no damage was observed anywhere else on the structure, and treatment is recommended unless the seller can prove prior treatment.
Fresh House generated structured findings from a documented professional record.
10651 Dunkeld Circle
St. Louis, Missouri
St. Louis, Missouri
- Home InspectionWhole-home inspection of single-family property at 10333 Lilac Ave, St Louis, MO found the home in generally good shape with no structural deficiencies; five items flagged for repair or attention across exterior, roof, electrical, and plumbing systems.
- RoofShingled roof is estimated 10 years old with patching/repairs present; one shingle has come loose and needs to be reattached.
- ElectricalSmoke detectors are inoperable and need to be replaced with functioning smoke detectors; Siemens 100-amp service panel with breakers appears functional.
- PlumbingLoose vanity sink faucet in bathroom needs to be secured; kitchen sink water pressure is very low, likely due to a clogged filter screen in the faucet; Ruud 38-gallon natural gas water heater (manufactured 2005) appears functional.
- HVACLennox forced-air gas furnace (manufactured 2005) and Lennox 2-ton split-system condenser (manufactured 1998) both appear functional; furnace is over 10 years old and should be checked, cleaned, and serviced yearly by a licensed contractor.
- FoundationPoured concrete basement foundation shows no moisture detected and no deficiencies observed in walls; perimeter insulation is not visible and adding insulation is suggested.
- UnclassifiedExterior covering (lap wood siding and asbestos tiles) requires repair or replacement of damaged tiles, and wood siding at the front of the home needs to be scraped and painted.
Fresh House generated structured findings from a documented professional record.
10333 Lilac Avenue
St. Louis, Missouri
- Home InspectionWhole-home inspection of 10254 Valley Dr, St Louis, MO 63137 identified multiple electrical deficiencies, a rain-water ceiling leak, exterior siding/trim damage, missing smoke detectors, and an aging water heater, with no structural deficiencies observed.
- RoofRoof covering is 3-tab shingle and roll roofing estimated at 10 years old and rated satisfactory; ceiling damage in the middle bedroom is attributed to rain water leaking in during hard rains, indicating a potential roof leak; no gutters or downspouts are present.
- HVACCentral split system with DuCane forced-air gas furnace (manufactured 2021) and Coleman 2-ton electric AC condenser (manufactured 2022) both appear functional and rated satisfactory; kitchen exhaust fan for gas range is absent and installation is recommended.
- PlumbingCopper supply pipes and PVC waste pipes are satisfactory; General Electric 40-gallon natural gas water heater manufactured in 2007 appears functional but is approximately 16 years old.
- FoundationPoured concrete foundation with basement access inspected; no moisture detected, no structural deficiencies observed, and basement walls and floor rated satisfactory.
- PestNo termite damage or presence was observed; termite treatment appears to have been previously performed.
- UnclassifiedExterior trim damage on front corners of home and deteriorated hardboard siding over the front porch require repair.
- ElectricalMultiple electrical deficiencies noted: GFI outlet at carport is inoperable; bathroom GFI outlet will not reset and needs replacement; kitchen GFI outlet has hot and ground wires reversed and needs rewiring; electrical outlets near the utility area are inoperable despite breakers being on; smoke detectors are missing throughout the home including near basement gas appliances.
- WindowsExterior windows include vinyl, aluminum, and steel-framed basement windows, all rated satisfactory with no deficiencies noted.
Fresh House generated structured findings from a documented professional record.
10254 Valley Drive
- Home InspectionWhole-home inspection of single-family property identified multiple deficiencies across site, exterior, roofing, structure, electrical, HVAC, plumbing, and interior systems, including loose deck planks, missing/damaged fencing, foundation cracks, moisture intrusion, and various repair items.
- RoofMissing roof shingle on front of home, lifted shingles need pressed and sealed to prevent moisture intrusion, trees contacting and hanging over roof, and damaged fascia board next to chimney need to be addressed.
- FoundationCracks observed in block foundation at front corner of home require sealing, and mortar cracks along SW corner of basement show active moisture intrusion tracking to where the wall meets the floor.
- ElectricalMissing smoke detectors need replacement, tree limbs are pushing on overhead power lines (contact Ameren), GFCI outlet absent in laundry area, and ungrounded two-prong outlets are present throughout the home.
- HVACHVAC system appears functional but furnace (approx. 7 years old, Rheem 2015) and AC compressor (approx. 16 years old, American Standard 2006) both need cleaning and servicing by an HVAC technician; bathroom ventilator is inoperable and needs repair.
- PlumbingToilet is loose at the base and runs for an extended time — needs to be secured and valve flap adjusted; water heater (Envirotemp, 40 gal, natural gas, manufactured 2009) is aging and should be monitored.
- WindowsTwo windows have broken seals and need repair or replacement, one window has busted trim requiring repair, and several windows will not completely lock and need locking mechanisms adjusted.
- PestTermite damage observed to wood fence; no termite damage or active presence was observed to the structure, but annual treatment for termites and wood-destroying insects is recommended.
Fresh House generated structured findings from a documented professional record.
1009 Northdale Avenue
WHAT THE RECORDS SHOW
38 recordsLast updated Jul 3, 2026
Based on 38 documented records from April through July 2026, records most often show full home inspections covering HVAC, electrical, foundation, plumbing, and roof systems. Documented work also includes windows, pest, mold, and sewer assessments. Records to date show multi-system residential inspection work in the St. Louis area.
Contact Greensmith Home Inspection LLC
About this profile
How Fresh House sources records
Where does this work history come from?
Source-backed work history from uploaded property records.
Are full documents public?
Some source documents are redacted, private, or commissioned.
By the Numbers
Coverage Area
St. Louis City, St. Louis County, Saint Charles County, Warren County, Jefferson County
Inspections, repairs, photos, document what you know about a property.